5 cal error status 1, 6 cal error status 2, 7 electronic configuration status – Flowserve Logix 520MD+ DD User Manual

Page 21: 8 mode states status, 9 feedback loop status, 10 position status, 11 cycles/travel status, 12 actuation status, 13 friction status, 14 control status

Advertising
background image

DD User Manual - Logix® 520MD+ Series Digital Positioner FCD-LGENSF0013-01

© Flowserve Corporation

21


Calibration in Progress, Analog Output Calibration In
Progress, and Jog Calibration Set 100% Position.

8.4.5

Cal Error Status 1

Select DO in slot 1 to trigger on Position Range Too Small,
Position Sensor Below ADC Range, Position Sensor Above
ADC Range, No Motion Time Out, Settle Time Out, and Inner
Loop Offset Time Out.

8.4.6

Cal Error Status 2

Select DO in slot 1 to trigger on Analog Output Range Too
Small, Command Input Range Too Small, Command Input
Below ADC Range, Command Input Above ADC Range,
Stroke Shift, Stroke Span Increase , and Stroke Span
Decrease.

8.4.7

Electronic Configuration Status

Select DO in slot 1 to trigger on Aux Card 1 Present, Aux
Card 2 Present, Pressure Sensor Board Present, and LCD
Present.

8.4.8

Mode States Status

Select DO in slot 1 to trigger on Factory Reset State,
Calibration in Progress, Signature or Partial Stroke Test in
Progress, Jog Command Mode, Partial Stroke Test
Scheduled, and DI Command Override.

8.4.9

Feedback Loop Status

Select DO in slot 1 to trigger on Position Deviation Alarm,
Position Sensor Failure Alarm, Valve Opened Too Far
Warning, Valve Closed Too Far Warning, Backlash Warning,
Backlash Alarm, Partial Stroke Test Failed Warning, and
Continuous Stroke Test Failed Warning.

8.4.10

Position Status

Select DO in slot 1 to trigger on Position High Limit Alert,
Position Low Limit Alert and Feedback Linkage Alarm.

8.4.11

Cycles/Travel Status

Select DO in slot 1 to trigger on Valve Cycles Warning, Valve
Travel Warning, Actuator Cycles Warning, Actuator Travel
Warning, Bellows Cycles Warning, Bellows Travel Warning,
Pilot Relay Cycles Warning, and Pilot Relay Travel Warning.

8.4.12

Actuation Status

Select DO in slot 1 to trigger on Supply Pressure High
Warning, Supply Pressure Low Warning, Supply Pressure
Low Alarm, Actuation Ratio Warning, Spring Unable to Fail
Safe Warning, Pneumatic Leak Warning, Air Supply Humid
Warning, and Air Supply Icing Warning.

8.4.13

Friction Status

Select DO in slot 1 to trigger on Friction High Warning,
Friction High Alarm, Friction Low Warning, Friction Low
Alarm, Valve Can't Open Alarm, and Valve Can't Shut Alarm.

8.4.14

Control Status

Select DO in slot 1 to trigger on Command Frequency
Warning, Command Frequency Alarm, Command Amplitude

Warning, Command Amplitude Alarm, Position Frequency
Warning, Position Frequency Alarm, Position Amplitude
Warning, and Position Amplitude Alarm.

8.4.15

Inner Loop Status

Select DO in slot 1 to trigger on Pilot Relay Response
Warning, Pilot Relay Response Alarm, Piezo Voltage High
Warning, Piezo Voltage High Alarm, Piezo Voltage Low
Warning, Piezo Voltage Low Alarm, and Driver Module
Alarm.

8.4.16

Main Board Status

Select DO in slot 1 to trigger on Main Board Electronic
Failure Warning, Software Error Warning, Memory Error
Warning, Temperature High Warning, and Temperature Low
Warning.

8.4.17

Electronic Board Status

Select DO in slot 1 to trigger on Aux Card 1 Failure Warning,
Aux Card 2 Failure Warning, Aux Card 1 No Loop Power,
Aux Card 2 No Loop Power, Aux Card 1 Error, Aux Card 2
Error, Pressure Sensor Board Failure Warning, and Low
Battery Warning.

8.4.18

Stroke/Friction Status

Select DO in slot 1 to trigger on Reversed Spring, Insufficient
Spring, and No Spring.

8.4.19

Main Board Status

Select DO in slot 1 to trigger on Humidity Sensor Failure,
Oscillator Fault, Position Sensor ADC Failure, Supply
Voltage Error, Reference Voltage Error, Shunt Voltage Error,
and Piezo Voltage Error.

8.4.20

Electronic Comp Status

Select DO in slot 1 to trigger on Pilot Can't Open, Pilot Can't
Shut, Hall Sensor Failure, and ILO Out Of Range.

8.4.21

Software Status

Select DO in slot 1 to trigger on NVMEM CRC Error, RAM
Error, RAM CRC Error, FLASH CRC Error, Watch Dog Time
Out, Stack Overflow Warning, CPU Usage Warning, and
Firmware Update Applied.

8.4.22

Press Cal Status

Select DO in slot 1 to trigger on Port S Out Of Range, Port A
Out Of Range, Port B Out Of Range, Port S Range too
Small, Port A Range too Small, Port B Range too Small, and
Pressure Sensor Failure.

8.5

Calibrate MFC 1 Analog Out

If the card in slot 1 is an Analog Output, perform an analog
output calibration.

8.6

Auxiliary Card 2 ID

View the auxiliary card present in slot 2. This feature is only
present if there is an auxiliary card in slot 2.

8.7

Auxiliary Card 2 Type

Advertising