Flowserve V901 VariCool Desuperheater User Manual

Page 8

Advertising
background image

- 8 -


Defect

No.

Possible cause

Remedy


Excessive valve seat leakage

4.1


4.2


4.3


damaged sealing edges at
valve seat or plug

foreign particles in seat area


plug does not close fully

contact customer services
department or contract partner

contact customer services
department or contract partner

refer to 3.1 to 3.5


Leaking stuffing box system

5.1




5.2








5.3


5.4


compression force on packing
too low



worn packing








dirty spindle


damaged spindle

slightly re-tighten stuffing box packing

Caution: make sure the valve spindles
can still move !

slightly re-tighten stuffing box packing

Caution: make sure the valve spindles
can still move !

if the packing does not stop leaking,
contact customer service department
or contract partner

clean spindle with suitable cleaning
agent

contact customer services
department or contract partner


Leaking top or lid seal

6.1


6.2

pressing force on seal(s) too
low

seal(s) defective

properly re-tighten top or lid nuts
crosswise

contact customer services
department or

contract partner


Leaking housing

7.1


medium or flow related damage

contact customer service department
or

contract partner


No limit switch signal

8.1


8.2

power supply to limit switch
interrupted

limit switch misadjusted

check power supply ( voltage, circuit
breakers, connections )

readjust limit switch; operating
distance see limit switch data sheet


Vibrating positioner

9.1

defective positioner

see maintenance and operating in
structions of positioner manufacturer


If the problem is not solved by taking the above measures, contact the customer services
department or contract partner.