Flowserve BUSwitch with Foundation Fieldbus Communications Protocol User Manual

Page 3

Advertising
background image

AXENIM0048-01 (Firmware Rev. Nov. 12 99) (AUTO-48) 11/01

Page 3 of 16

©2001, Flowserve Corporation, Springville, UT

Flowserve Corporation

1350 South Mountain Springs Parkway

Phone: 801 489 2233

Flow

Control

Division Springville,

Utah

84663

Facsimile:

801

489

2228

Automation

Business

Unit www.flowserve.com

Email:

[email protected]

Automax Valve Automation Systems

Product Specification

Printed Circuit Board Specifications

Power Requirements: Communications Card

XA0239

Communications Card

Bus powered
9.5-32 VDC at 14 mA

Power requirements: 2-Wire Version

XA0338 Interface Card

Version 2.0

Bus-Powered by XA0239

Communication Card

Power requirements

: 4-Wire Version

XA0242 Interface Card

24 VDC

x

10 mA quiescent

x

510 mA max. with

solenoid activated.

Temperature

Operational

-40 °F to +185 °F
(-40 °C to +85 °C)

Storage

-40 °F to +250 °F
(-40 °C to +120 °C)

To operate, an external 24 VDC source must be locally

supplied to the interface card.

Intrinsically

Safe

Entity

Parameters

(FR-Series BUSwitch only)

Class 1, Div. 1, Groups A-G & ATEX EEx ia IIC T4
V max = 24V, I max = 250mA
Ci = 5 nF, Li = 8 µH

FOUNDATION

£

Fieldbus Information

Manufacturer

ID 0x46

4C4F

(Hex)

Name

46 6C 6F 77 73 65 72 76 65

F l o w s e r v e

Device

Type 0x50

53

(Hex)

ID 464

C4F5053:BUSWITCH:xxxxxx

Max length of 32 characters. Characters

21 through 32 are used for board serial

number.

Device Descriptions are supplied on included diskette

or can be downloaded from the Fieldbus Foundation

website (www.fieldbus.org).

Start-up Guide


1. Following the instructions in “Mechanical Installation,”

install the BUSwitch™ onto a pneumatic actuator and

turn supply air on.

2. Following the instructions in “Electrical connections,”

connect fieldbus and optional dry-contact wiring.

3. Referring to control system or configuration system

documentation, install BUSwitch™ device description

(DD) files onto system hard drive. Note: Readme file
on DD floppy contains instructions.

4. Initialize communications with device and bring up the

“Live List.” BUSwitches have been

configured from

the factory with an ID of “464C4F5053:BUSWITCH:

[serialnumber]” and a default tag of “FLOWSERVE

BUSWITCH.” Note the serial number.


5. Change the BUSwitch™ attribute Device ID to the

value noted in step 4 and change the Device Tag to

the appropriate value.

6. Assign the Tag configuration in step 5.

7.

BUSwitches are shipped with resource block,

transducer block, (2) DO blocks and (4) DI blocks pre-

configured unless specially configured by agreement

with customer. Refer to the appropriate sections in

this manual for the default configuration. Make any

desired changes to this configuration and download.




CAUTION

The BUSwitch may cycle during a configuration
download. Exercise caution in handling valves
that may be stroked during these procedures.

For best results, Flowserve strongly
recommends reading this entire document
before attempting to configure and commission
BUSwitches.

Note: For Fisher DeltaV systems, the DD files
must be copied to a directory or folder named
“464C4F” in order for the system to find them.