Flowserve BUSwitch with Foundation Fieldbus Communications Protocol User Manual

Page 16

Advertising
background image






AX

ENIM0048-01 (Firmware Rev. Nov. 12 99) (AUTO-48) 11/01

Page 16 of 16

©2001, Flowserve Corporation,

Springville, UT

Flowserve Corporation

1350 South Mountain Springs Parkway

Phone: 801

489 2233

Flow

Control

Division Springville,

Utah

84663

Facsimile:

801

489

2228

Automation

Business

Unit www.flowserve.com

Email:

[email protected]

Automax Valve Automation Systems

Product Specification

18

CHANNEL

1 for DI-1
2 for DI-2
3 for DI-3
4 for DI-4

The number of the logical hardware channel that is connected to this I/O
block. This information defines the transducer to be used going to or
from the physical world.

19

FSTATE_TIME

The time in seconds from detection of fault of the output block remote
setpoint to the output action of the block output if the condition still
exists.

20

FSTATE_VAL_D

The preset discrete SP_D value to use when fault occurs. This value will
be used if the I/O option Fault State to value is selected.

21

BKCAL_OUT_D

The output value and status provided to an upstream discrete block.
This information is used to provide bumpless transfer to closed loop
control.

22

RCAS_IN_D

Target setpoint and status provided by a supervisory Host to a discrete
control or output block.

23

SHED_OPT

***

Defines action to be taken on remote control device timeout.

24

RCAS_OUT_D

Block setpoint and status provided to a supervisory Host for back
calculation and to allow action to be taken under limiting conditions or
mode change.

25

UPDATE_EVT

This alert is generated by any change to the static data.

26

BLOCK_ALM

The block alarm is used for all configuration, hardware, and connection
failure or system problems in the block. The cause of the alert is entered
in the subcode field. The first alert to become active will set the Active
status in the Status attribute. As soon as the Unreported status is
cleared by the alert reporting task, another block alert may be reported
without clearing the Active status, if the subcode has changed.

*** = NormalShed_NormalReturn