PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12

58

Redundant PROFIBUS DPV1 Wiring Diagram

CONTROL PANEL

SENSOR

POSITION

SENSOR

TORQUE

SENSOR

THERMAL

24V DC +Ve

0V DC

DIG COM #3-Ve

33

GR

OUP 3

CONTROL

SUPPLY

SEE

2

NOTE

DIG COM #3A

INPUT 0

32

30

DIG COM #2-Ve

31

DIG COM #2A

INPUT 1

29

34

INPUT 2

35

GR

OUP 2

OPEN

28

DIG COM #1-Ve

STOP

25

26

CLOSE

27

GR

OUP 1

21

22

0% OPEN

STATUS OK

OPEN

CLOSE

(YES)

(NO)

REMO

TE

LOCAL

(SEE NOTE 4)

MOTOR

"CLOSE"

POSITION

"OPEN"

POSITION

(SEE NOTES 3 & 5)

RELAYS

PRIMARY

50

51

47

46

48

49

45

44

S2

S1

a

b

a

b

- 5W MAX. EXT. LOAD

2. REMOTE INPUT JUMPERS

INPUT 0 - ESD,

INPUT 1 - OPEN INHIBIT,

INPUT 2 - CLOSE INHIBIT.

1. REMOTE INPUTS

DEFAULT INPUT CONFIGURATION:

POLARITIES ARE CORRECT.

JUMPERS CAN BE USER WIRED TO CONNECT DIG COMMONS

#1, 2 & 3 (AS NEEDED). THE 3 REMOTE WIRING GROUPS

ARE ELECTRICALLY ISOLATED, INTERNALLY. ONLY A SINGLE

POWER SOURCE MAY BE USED TO POWER ANY ONE GROUP

BUT DIFFERENT SOURCES MAY POWER DIFFERENT GROUPS.

IF DIFFERENT SOURCES ARE USED, ENSURE THAT THE

4. MAXIMUM EXTERNAL LOAD

REQUIRED CONTROL SIGNAL DURATION = 350ms MIN.

2 mA / 24V DC

MAX LOAD - 10 mA / 110V AC

MAXIMUM "OFF" 5.0V AC/DC

SIGNAL THRESHOLD - MINIMUM "ON" 19.2V AC/DC

INPUTS 0,1,2 ARE FIELD CONFIGURABLE FOR

CLOSE/OPEN INHIBIT, USER INPUT, OR ESD.

IN ADDITION, INPUT 2 MAY BE CONFIGURED

FOR CSE REMOTE SELECTION INDICATION.

TERMINALS 21 AND 22 (24 VDC)

3. DEFAULT [S] SETTINGS

THE DEFAULT OPERATING CONFIGURATION FOR THE

"S" OUTPUTS ARE SHOWN IN THE TABLE BELOW.

THE CONTACT STATES SHOWN IN THE SCHEMATIC

REPRESENT A FULLY CLOSED VALVE.

OUTPUT SWITCH CONTACT DEVELOPMENT

VALVE POSITION

FULL

CLOSE

FULL

OPEN

FUNCTION

CLOSE LIMIT

OPEN LIMIT

S1a

OUTPUT

SWITCH

OPEN CONTACT

CLOSED CONTACT

S2b

S2a

S1b

SEE OPERATION MANUAL FOR ALTERNATE CONFIGURATIONS.

5. CONTACT RATINGS

S1, S2- 0.5 AMP @ 125 VAC, 2 AMPS @ 30 VDC (RESISTIVE)

MONITOR- 0.5 AMP @ 125 VAC, 2 AMPS @ 30 VDC (RESISTIVE)

6. COMMAND PRIORITY

PLEASE SEE INSTALLATION AND OPERATION MANUAL

LMENIM 3306 FOR NETWORK COMMAND PRIORITIES.

POWER SUPPLY

PBDP-A OUT (+)

PBDP-A OUT (-)

SEE NOTES

3

14
13

4
5

PBDP-A IN (+)

PBDP-A IN (-)

PER IEC 61158-2

REDUNDANT PROFIBUS DPV1 (BOARD 2)

PBDP-B OUT (+)

PBDP-B OUT (-)

15
16

1

2

PBDP-B IN (+)

PBDP-B IN (-)

PER IEC 61158-2

SINGLE MASTER REDUNDANCY NOTES:
1. FOR SINGLE MASTER REDUNDANCY, JUMPER

13/14 FROM BOARD 1 TO 16/15 ON BOARD 2,

2. DATA IN ON 13 AND 14.

3. DATA OUT ON 4 AND 5.

DUAL MASTER REDUNDANCY NOTES:

1. FOR DUAL MASTER REDUNDANCY,

DO NOT INSTALL JUMPERS AS SHOWN.

2. FOR INTERFACE 1; DATA IN ON 13 AND 14,

DATA OUT ON 4 AND 5.

3. FOR INTERFACE 2; DATA IN ON 16 AND 15,

DATA OUT ON 1 AND 2.

AS SHOWN.

PRIMARY PROFIBUS DPV1 (BOARD 1)

SURGE

Advertising