Channel 344 – Set Actuator Position (Index 104)

This channel, AO_CTRL_VALVE_FLOW_CHAN, is used to set the position of the actuator when it is
locally configured to run in the Position mode.

Control valve is in units of 0-100%.

AO_CTRL_VALVE_FLOW_CHAN will only function when the actuator is in Position mode. Position
mode is selected using the setup menus; refer to Bulletin LMENIM2306.

Channel 347 – Position and Bus Mode (Index 107)

This channel, DI_POSITION_AND_BUS_MODE_CHAN, makes actuator status information available to
other function blocks. The status information describes the position of the actuator (open or closed)
the direction of motion of the actuator (opening or closing), and the operating mode (Local, Remote,
or Stop [off]).

Channel 347

DI_POSITION_AND_BUS_MODE_CHAN

Value

Opened + Remote

0x21

Closed + Remote

0x22

Opening + Remote

0x24

Closing + Remote

0x28

Stop + Remote

0x30

Opened + Local

0x41

Closed + Local

0x42

Opening + Local

0x44

Closing + Local

0x48

Stop + Local

0x50

Opened + Stop

0x81

Closed + Stop

0x82

Opening + Stop

0x84

Closing + Stop

0x88

Stop + Stop

0x90

Channel 348 – Position Channel (Index 108)

This channel, DI_POSITION_CHAN, makes actuator status information available to other function
blocks. The status information describes the position or direction of motion of the actuator, that is,
either Opened, Closed, Opening, Closing, or Stop.