Flowserve MX/QX Profibus DP/PA Field Unit User Manual

Page 78

Advertising
background image

PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12

78

Parameter

Transducer Block Description

TQ_STATUS
(Index 99)

Manufacturer-specific parameter that contains an array in 16-bit word format:
Array Index 0: Unused
Array Index 1: MB_TQ_C_Avg_Last
Array Index 2: MB_TQ_O_Avg_Last
Array Index 3: MB_TQ_O_Peak_Last
Array Index 4: MB_TQ_O_Breakout_Last
Array Index 5: MB_TQ_C_Breakout_Last
Array Index 6: MB_TQ_O_Ending_Last
Array Index 7: MB_TQ_C_Ending_Last
Array Index 8: MB_TQ_C_Peak_Last
Array Index 9: MB_TQ_O_Peak_Ref
Array Index 10: MB_TQ_O_Breakout_Ref
Array Index 11: MB_TQ_C_Breakout_Ref
Array Index 12: MB_TQ_O_Ending_Ref
Array Index 13: MB_TQ_C_Ending_Ref
Array Index 14: MB_TQ_C_Peak_Ref

TRAVEL_LIMIT_LOW
(Index 63)

Lower limit of the valve position in percent of travel span.

TRAVEL_LIMIT_UP
(Index 64)

Upper limit of the valve position in percent of travel span.

TRAVEL_RATE_DEC
(Index 65 – Not Used)

Configurable time for full-span change (closing time of the valve) in seconds.

TRAVEL_RATE_INC
(Index 66 – Not Used)

Configurable time for full-span change (opening time of the valve) in seconds.

VALVE_MAINT_DATE
(Index 67)

Date of last valve maintenance.

VALVE_MAN
(Index 75)

Name of valve manufacturer.

VALVE_SER_NUM
(Index 80)

Serial number of the valve belonging to the positioner or electronic device.

VALVE_STATUS
(Index 98)

Manufacturer-specific parameter that contains an array in 16-bit word format:
Array Index 0: Requested relay channel value
Array Index 1: Status Register – Modbus Register 9
Array Index 2: Fault Register – Modbus Register 10
Array Index 3: Digital Output Register – Modbus Register 11
Array Index 4: Digital Input Register #1 – Modbus Register 12
Array Index 5: Digital Input Register #2 – Modbus Register 13

VALVE_TYPE
(Index 77)

Type of valve:
0 = linear moving valve, sliding valve
1 = rotary moving valve, part-turn
2 = rotary moving valve, multi-turn

FD_FIRMWARE_VERSION
(Index 120)

Internal field device firmware version (Read-only USIGN16 Hex value).

TORQUE
(Index 121)

Torque parameter record (Read-only).

Members:

Data type

Description

USIGN8

CLOSE_SETTING value in percent of unit rating.

USIGN8

OPEN_SETTING value in percent of unit rating.

USIGN8

BOOST_SETTING value 1 = On, 2 = Off, 4 = Auto.

USIGN8

OUTPUT value in percent of unit rating.

Advertising