Worcester controls – Flowserve 10 ACCESS I Worcester Controls User Manual

Page 4

Advertising
background image

4

10, 15, 20 ACCESS I and 10-40 Access M 39 Actuators Intrinsically Safe

WCAIM2028

3. Switches have been factory adjusted, but should be rechecked

after installation. Adjustment is as follows:

a) Switch adjustment for “standard” mounting:

With actuator mounted in “standard” mounting
configuration (see Step 1) set actuator in full-closed
position with the adjustment screw near its loose limit.
Adjust closed position switch SW-2 (see Wiring Diagram)
by tightening the adjustment screw until switch contacts
click. Then tighten adjustment screw one additional turn.
With air supply to actuator, energize solenoid, if applicable,
cycle to the full-open position and adjust open position
switch SW-1 in the same manner.

b) Switch adjustment for FAIL-OPEN mounting:

With actuator mounted in FAIL-OPEN mounting
configuration (see Step 2) set actuator in full-open position
with the adjustment screw near its loose limit. Adjust open
position switch SW-2 (see Wiring Diagram) by tightening
the adjustment screw until contacts click. Then tighten
adjustment screw one additional turn. With air supply to
actuator, energize solenoid, if applicable, cycle to the full-
closed position and adjust closed position switch SW-1 in
the same manner as SW-2.

4. Wiring instructions for solenoid and/or limit switches:

The Intrinsically Safe solenoid valve used in the ACCESS is
designed to operate on power levels compatible with Intrinsic
Safety requirements. They are Factory Mutual (FM) approved
for Class I, II and III Groups A, B, C, D, E, F, and G
applications. Entity Approval #OT4A6.AX (NFPA 493; July 19,
1990).

NOTE 1: For barrier interconnection, refer to maximum barrier
output parameters as referenced on the specific barrier
Installation drawing. Connect as follows:

a) V max > Voc of single or Vt of dual channel barrier.

b) I max > Isc of single or It of dual channel barrier

c) Ci + field wiring < Ca of single or dual channel barrier

d) Li + field wiring < La of single or dual channel barrier

For current and wattage values at various input voltages see
table below.

Input Voltage

Current

Wattage

15.5 VDC

43 mA

.7

24 VDC

68 mA

1.63

35 VDC

95 mA

3.3

Make electrical connections in accordance with the
appropriate wiring diagram on inside of cover or the
appropriate diagram in figure 3:

NOTE 2: Installation of Intrinsically Safe Systems is to be done
in accordance with Canadian Electrical Code, Part 1 and
National Electrical Code, Chapter 1.

DEFINITIONS:

Ca-Maximum Allowed Capacitance

Li-Maximum Internal Inductance

Ci-Maximum Internal Capacitance

Voc-Maximum Output Voltage

I max-Maximum Input Current

V max-Maximum Input Voltage

Isc-Maximum Output Current

Vt-Voltage Total

La-Maximum Allowed Inductance

Flow Control

Worcester Controls

Figure 3

FAIL-CLOSED

(Sizes 10–40 in-line operation)

(Sizes 25–40 cross-line operation)

FAIL-OPEN

(Sizes 10–20 in-line, inverted operation)

Advertising