System malfunctions, Operation malfunctions – Flowserve NRR 2-40 User Manual

Page 26

Advertising
background image

26

LED “Power” flashes slowly.

Fault:

The power supply unit (PSU) is overloaded and may be misused for other
components.

Remedy: Check load of power supply unit. Be sure to use the PSU only for the

voltage supply of bus-based network components.

Disconnect the system from its power supply. After 5 sec. apply power
and restart system.

System malfunction 4

System Malfunctions

– continued –

LED flashes slowly

Fault:

Power supply unit defective.

Remedy: Replace PSU.

The terminal strip of the NRR 2-40 is live during operation.
This presents the danger of electric shock.
Cut off power supply before mounting or removing the equipment.

Device does not work – no function

Fault:

LED “Power” does not light up.

Remedy: Apply power. Connect the equipment properly, referring to wiring

diagrams.

Operation Malfunctions

Attention

Fault-finding list for troubleshooting