Fig. 17 (Factory setting of neutral band)

Annex

– continued –

To guarantee a smooth controlled system you can establish a neutral band for the
setpoint W. The setpoint is defined by the proportional band which is determined by
switch point 2 and 3.

Detach terminal strip in order to set code switch .

Neutral band

The terminal strip of the NRR 2-40 is live during operation.
This presents the danger of electric shock.

Cut off power supply before fixing or removing the housing lid or terminal
strips.

Warning

8

A

Establishing / changing neutral band

Note down current node ID and baud rate.

Node ID in this example “40”

Baud rate in this example

250 kBit/s”

Switch off mains voltage.

The four status LEDs go out.
The LED “Power” goes out.

LED “Power” extinguished