Commissioning procedure, Fig. 14 – Flowserve NRS 1-51 User Manual

Page 17

Advertising
background image

7

Commissioning Procedure

Checking switchpoint and function

Start

Activity

Indication

Function

Apply mains voltage.

All LEDs are illuminated.

System is being started and tested, this takes

approx. 0 sec. Output contacts are open.

Signal output  closed.

All LEDs are illuminated for more

than 0 sec.

System malfunction. Possible causes:

Faulty power supply, level switch defective.

Lower water level in boiler

until the level falls below

the switchpoint high water

level (HW). Level electrode is

exposed.

Green LED

for level electrode  is illuminated

Output contacts are closed.

Signal output  is open.

Checking switchpoint and function

Raise level in boiler until the

switchpoint “high water level

(HW)” is ecxeeded. Level

electrode enters the water.

Red LED

for level electrode  is flashing

De-energizing delay is running.

Signal output  is closed instantaneously.

Red LED

for level electrode  is illuminated

Delay time has elapsed, output contacts open.

Signal output  is closed.

Possible installation faults

Status and indication

Fault

Remedy

Sightglass indicates high

water level (HW) exceeded,red

LED for level electrode  is

not illuminated. Safety circuit

closed.

The electrode rod is too short.

Replace electrode rod and cut new rod to the

length dictated by the switchpoint HW.

The earth connection to the vessel

is interrupted.

Clean seating surfaces and screw in level

electrode with metallic joint ring. Do not

insulate the electrode with hemp or PTFE

tape!

Electrical conductivity of the boiler

water too low.

Set response sensitivity of the level switch to

0.5 μS/cm.

If installed inside the boiler: Upper

vent hole in protection tube does

not exist or is obstructed.

Check installation of level electrode. Make

sure that the level in the protection tube cor-

responds to the actual water level.

Water level sufficient. Red

LED for level electrode  is

illuminated. Safety circuit is

open.

Electrode rod is too long.

Cut electrode rod to the length dictated by the

switchpoint HW.

Upper vent hole flooded.

Check installation of level electrode. Make

sure that the level in the protection tube

corresponds to the actual water level.

Level electrode 1

Test & diagnosis

button

LED alarm  /

operating mode

Diagnosis LED

Fig. 14