Troubleshooting – Flowserve NRS 1-51 User Manual

Page 19

Advertising
background image

9

Diagnosis

Display 1 and activity

Display 2

Fault

Remedy

LED alarm  and

diagnosis LED 

illuminated. Press and hold

down

key 1.

Diagnosis

LED 

flashing.

Malfunction in level

electrode , malfunction in

level switch, faulty wiring,

faulty measuring voltage.

Check wiring,

replace level switch.

Diagnosis

LED 

flashing.

Malfunction in level

electrode , malfunction in

level switch, faulty wiring.

Diagnosis

LED 3

flashing.

Interference voltage causing

malfunction, boiler earth

without PE

Provide screen and earthing, connect

boiler with PE.

LED alarm  or 

and Diagnosis LED 3

illuminated. Press and hold

down

key 1 or 2.

Diagnosis

LED 

flashing.

Malfunction in processor,

stand-by fault.

Observe operating instructions for the

logic unit SRL. Replace level switch.

Diagnosis

LED 

flashing.

Internal voltage fault.

Replace level switch.

Diagnosis

LED 3

flashing.

Malfunction in relay.

Once the fault is eliminated, the level switch returns to normal operation.

After elimination of the fault switch off the mains voltage and switch it on again after approx. 5 sec.

Further fault indications

Status

Diagnosis

Function

Next activity

Faulty evaluation of level

electrode , channel 

Diagnosis LED  and

LED alarm  illuminated.

Output contacts are opened instantaneously.

Signal output  closes instantaneously.

next:

Press

key 1.

Malfunction in level

switch detected.

Diagnosis LED 3 and

LED alarm  or 

illuminated.

Output contacts are opened instantaneously.

Signal outputs / are closed instantaneously.

next:

Press

key 1

or key 2.

Troubleshooting

– continued –

Indication, diagnosis and remedy

– continued –

Malfunction in level electrode

Status and indication

Fault

Remedy

Water level sufficient. Red

LED for level electrode  is

illuminated. Safety circuit is

open.

The insulation of the level

electrode is dirty or faulty.

Clean or, if necessary, replace level electrode.

If faults occur that are not listed above or cannot be corrected, please contact our service centre or