Operation, alarm and test – Flowserve NRA 1-3 User Manual

Page 16

Advertising
background image

6

Function of keys

Key :

Reduce value –, browse

Key 3:

Increase value +, browse

Key  (E): Press briefly: Call up/Execute menu // Continue / Save settings

Key  (E): Press longer: Return to menu, cancel input

Key  + 3: Press longer: Reset/Delete values (e. g. alarm list + maintenance interval)

LEDs 1 – 3

LED :

Steam loss

LED :

Banking-up of condensate

LED 3:

Measuring electrode NRG 6-7 defective (short circuits, parting of a cable).

Measuring electrodes NRG 6-9 are not monitored.

Operation, Alarm and Test

Specification of keys and displays

E

Fig. 6

Key to codes on seven-segment display

Code

Meaning

The following codes can appear on the seven-segment display even if no key is being pressed:
SYS

System

SYS changes with plant temperature in °C

E.0

Error

Incorrect configuration due to inadmissible code switch setting

E.0

Error

In mode  and 7 the settings for banking-up of condensate is not finished

E.03

Error

Maintenance interval (6 months) elapsed

C.0 – C.6

Channels  - 6

Indication of measuring channel

If the E key is pressed:
HIS

History

Alarm list detailing old alarms

InT

Interval

Remaining time of maintenance interval

CAL

Calibration

Channel calibration in mode 

dtC (mode , 7)

Delta TC

Admissible deviation from condensate temperature in steam trap

dtS (mode , 6)

Delta TS

Admissible deviation from plant temperature

tSt

Test

LEDs and all segments are illuminated

ALL

All channels

Channel selection when calibrating / setting

C.0 – C.6

Channels  - 6

Indication of measuring channel

don

Done

Confirmation of input when setting parameters

clr

Clear

Confirmation of clear command (interval, alarm)