Technical data – Flowserve NRA 1-3 User Manual

Page 6

Advertising
background image

6

NRA 1-3

Technical Data

Supply voltage

30 V, 50 / 60 Hz

5 V, 50 / 60 Hz optional
Input

6 inputs for measuring electrodes NRG 6-9, NRG 6-7, NRG 6-8

 input for temperature sensor, e. g. TRG 5-63, temperature sensing element Pt 00
Output

 volt-free relay contact

Contact material: AgNi 0,5

Max. contact rating for switching voltages of 4 V AC/DC, 5 V AC and 30 V AC:

4 A resistive / inductive
Electrode voltage

 V
Banking-up of condensate setting

Difference temperature condensate/installation

dts  K to 00 K, adjustable in steps of  K

(mode  and 6)

Difference temperature condensate/switchpoint banking-up of condensate

dtC  K to 00 K,

adjustable in steps of  K (mode  and 7)

Switchpoint banking-up of condensate 0 °C to 55 °C, adjustable in steps of 5 K (mode  and 7)
Indicators and adjustors

 Three-digit seven-segment LED display, red, for indicating faulty steam traps and status and error

messages

3 LEDs for indicating banking-up of condensate, steam loss and malfunction in measuring electrode

3 Pushbuttons for parameter settings

 Ten-pole code switch for system configuration
Delay of response

max. 5 sec.
Power consumption

max. 4 W
External fuse

63 mA
Design

NRA -3a: for wall mounting

NRA -3e: for panel mounting
Protection

NRA -3a: IP 65 to EN 6059

NRA -3e: Front: IP 65 to EN 6059, back: IP 00
Protection class

NRA -3a:  (completely insulated)
Max. admissible ambient temperature

55 °C
Enclosure

Material: ABS