Flowserve NRA 1-3 User Manual

Page 5

Advertising
background image

5

Scope of supply

NRA 1-3

 Test station NRA -3

 Installation manual

Explanatory Notes

Description

The measuring electrode detects banking-up of condensate and steam loss either directly in the steam

trap or in separate test chambers.
The measuring electrodes NRG 6-7, NRG 6-8 feature an additional temperature sensor for

measuring the temperature of the condensate.
Up to 6 measuring electrodes and a temperature sensor for measuring the temperature of the installa-

tion can be connected to the test station NRA -3.

Function

The following electrodes can be used for monitoring steam traps:

n

Measuring electrode NRG 6-9 for detecting banking-up of condensate or steam loss (electrode

submerged or exposed)

n

Measuring electrode NRG 6-7, NRG 6-8 for detecting steam loss and banking-up of conden-

sate, with the condensate temperature being measured by an integrated temperature sensor

Three LEDs indicate banking-up of condensate, steam loss and malfunction in measuring electrode

(cable disruption, short circuit) and a three-digit seven-segment display shows the number of the

faulty steam trap. If more than one steam trap are defective the numbers of the faulty traps are

indicated one after another.
If banking-up of condensate, steam loss or malfunction in measuring electrode is indicated, an output

relay for the collective alarm will also be energised.
When using the measuring electrodes NRG 6-7, NRG 6-8 you can set the switchpoint for the

message “Banking-up of condensate” as a function of the separately detected temperature of the

installation or of the temperature measured in the steam trap.
The seven-segment display indicates every 6 months the maintenance interval of the measuring

electrodes in the form of an error code.
The seven-segment display indicates also status and error messages.

System components

TRG 5-63 (e. g.)

Temperature sensor with resistance thermometer Pt 00 for measuring the temperature of the

installation.
NRG 16-19

Measuring electrode for detecting banking-up of condensate or steam loss (electrode submerged or

exposed).
NRG 16-27, NRG 16-28

Measuring electrode for detecting banking-up of condensate or steam loss (electrode submerged or ex-

posed) with integrated temperature sensor PT 000 for measuring the temperature of the condensate.