Wiring – Flowserve NRG 16-38S User Manual
Page 17
Advertising
17
Note that screened four-core cable, e. g. I-Y(St)Y 2 x 2 x 0.8 or LIYCY 4 x 0.5 mm²
is required for wiring the electrode.
Max. cable length 100 m with conductivities from 10 µS/cm.
Max. cable length 30 m with conductivities from 0.5 µS/cm.
■
Fuse supply cables 250 mA (slow-blow).
Wiring
Tools
Attention
Wiring Diagram
■
Screwdriver for slotted screws, size 2.5, completely insulated to DIN VDE 0680-1
NRG 16-11
Fig. 10
Burner protection
circuit