Wiring – Flowserve NRG 16-38S User Manual

Page 17

Advertising
background image

17

Note that screened four-core cable, e. g. I-Y(St)Y 2 x 2 x 0.8 or LIYCY 4 x 0.5 mm²
is required for wiring the electrode.

Max. cable length 100 m with conductivities from 10 µS/cm.

Max. cable length 30 m with conductivities from 0.5 µS/cm.

Fuse supply cables 250 mA (slow-blow).

Wiring

Tools

Attention

Wiring Diagram

Screwdriver for slotted screws, size 2.5, completely insulated to DIN VDE 0680-1

NRG 16-11

Fig. 10

Burner protection
circuit

Mains