Malfunctions

If faults occur that are not listed above, please contact our subsidiary or agency in
your country.

Warning

The terminal strip of the NRGT 26-1 is live during operation. This presents
the danger of electric shock.

Cut off power supply before fixing or removing the housing cover.

Fault finding list for troubleshooting

The equipment fails to work

Fault:

Mains voltage has not been applied.

Remedy: Apply mains voltage. Wire equipment according to wiring diagram.

Fault:

The thermal fuse of the NRGT 26-1 has been activated.

Remedy: In case of a defective thermal fuse the mains voltage is not applied

across terminal . Replace thermal fuse.
Stock code 051629

The ambient temperature must not exceed 70 °C.

Fault:

The printed circuit board of the NRGT 26-1 is defective.

Remedy: Replace printed circuit board. Stock code 391360

Fault:

The internal joint ring of the electrode rod of the NRG 16-11 is damaged.

Remedy: Replace level electrode NRG 16-38 S / NRG 16-39 S.

The equipment does not work accurately

Fault:

Incorrect setting of the measuring range.

Remedy: Adjust switch properly, see “Basic Settings”.

Fault:

Dirt deposits have accumulated on the electrode rod.

Remedy: Replace level electrode NRG 16-38 S / NRG 16-29 S.