Operation – Flowserve UBK 46 User Manual

Page 15

Advertising
background image

15

Operation

The steam trap opens within its rated pressure/temperature range at the opening temperature set at
our works. The opening temperature adjusted at our factory can be increased or decreased by max.
40 K. Fig. 2, Fig. 4

1. Observe danger note on page 4.

2. Unscrew body screws A and remove cover C from body G. Fig. 2

3. Wait until regulator D has cooled down to ambient temperature.

4. To increase the discharge temperature turn setscrew K of the regulator max. one turn to the left.

1

/

8

of a turn corresponds to 5 K. Fig. 3

5. To decrease the discharge temperature turn setscrew K of the regulator max. one turn to the

right.

1

/

8

of a turn corresponds to 5 K. Fig. 3

6. Replace gasket F when damaged. If the cover C is new or taken from another trap the gasket F

has to be replaced.

7. Assemble cover and body. Tighten screws alternately to a torque of 25 Nm in several steps.

Adjust discharge temperature

Spanner 16 mm A. F. to DIN 3113, form B

Screwdriver size 3.5 to DIN 5265

Tools