Maintenance – Flowserve UBK 46 User Manual

Page 17

Advertising
background image

17

1. Observe danger note on page 4.

2. Unscrew body screws A and remove cover C from body G.

3. Unscrew, clean and check regulator D. Do not disassemble the regulator.

4. Replace regulator D in case of visible signs of damage or wear.

5. Clean body and internals. Clean all gasket surfaces.

6. Apply heat-resistant lubricant to all threads and sealing surfaces of the regulator and cover (use for

instance WINIX

®

2150).

7. Screw in regulator and tighten with a torque of 90 Nm.

8. Replace gasket F when damaged. Use the same cover C. If the cover C is new or taken from

another trap the gasket F has to be replaced.

9. Put cover onto the body. Tighten body screws A alternately to a torque of 25 Nm in several steps.

Clean / replace regulator

Clean / replace strainer

1. Observe danger note on page 4.

2. Loosen sealing plug J and unscrew together with strainer H.

3. Clean strainer, sealing plug and gasket surfaces.

4. Replace strainer und sealing plug in case of visible signs of wear or damage.

5. Replace gasket H if damaged.

6. Apply heat-resistant lubricant to the thread of the sealing plug (e. g. WINIX

®

2150).

7. Mount sealing plug J with gasket I and strainer H. Tighten sealing plug with a torque of

120 Nm.

WINIX

®

is a registered trademark of WINIX GmbH, Norderstedt

The UBK 46 does not require any special maintenance. However, if used in new installations which have
not been rinsed it may be necessary to check and clean the trap.

You can check the trap for steam loss with GESTRA’s ultrasonic measuring unit VAPOPHONE

®

or

the test unit TRAPTEST

®

. The contact points required for this functional check are on the name plate

of the cover.
In case of steam loss clean the trap or replace the regulator.

Check steam trap

Maintenance

Risk of severe scalds and burns to the whole body!

Before carrying out maintenance work or loosening flanged connections or sealing plugs,
make sure that all connected lines are depressurised (0 bar) and cooled down to room
temperature (20 °C).

Danger