EN-US

Technical Data

Max. input voltage in no-load operation

850 V

Max. input current

60 A

Max. input current per fuse holder

20 A

Max. number of strings (with integrated module fuse)

12

Max. cable cross section for terminals on the solar module side

6 mm²

Max. cable cross section for terminals on the inverter side

95 mm²

Screw joint for cable attachment to the solar module side

M16

Screw joint for cable attachment to the inverter side

M32

Protection type

IP 66

Protection class

II

Ambient conditions

-25°C - +55°C

-13°F -

+131°F

Dimensions (without screw joints)

330 x 440 x 137 mm

12.99 x 17.32 x 5.39 in.

-

1 Fronius DC Box 60/12

-

2 M32 metric screw joints including counter nuts

-

24 M16 metric screw joints including counter nuts

-

12 M16 threaded plugs

-

1 M20 metric screw joint including counter nut

-

1 M20 metric threaded plug

-

1 leafleat

As an option, you can also install a commercially-available overvoltage
protection in the Fronius DC Box 60/12.

Abbreviations
and Descripti-
ons Used

DC cable ‘OUT’

DC output cable from Fronius DC Box 60/12 to inverter.
The polarity of the DC cable ‘OUT’ depends on how
the solar module strings are connected to the Fronius
DC Box 60/12.

DC cable ‘IN’

Solar module strings from the solar modules to the
Fronius DC Box 60/12.
Each solar module string has one DC+ cable and one
DC- cable.

Scope of
supply

optional