Alarms, Alarm notifications, Alarm types – Geist Watchdog 100 User Manual

Page 18: Alarm removal, Thresholds

Advertising
background image

GM1118 - Watchdog 100 Series User
Manual

18

Revision Date: 2/16/2015

Alarms


Alarm Notifications

The Watchdog 100 supports three types of alarm notification:

Relay: The unit can be configured to energize/de-energize one control relay.

E-Mail: The unit can be configured to send alarm e-mails to up to three recipients.

SNMP: The unit can be configured to send SNMP traps to up to two trap servers.

Figure 19: Alarms Options


The unit is capable of any combination of the above alarms at once. Alarm type combinations
are selected per alarm via the check boxes which are displayed for each alarm on the Alarms
page.

Alarm Types

The Watchdog 100 provides three types of alarm messages via E-Mail and SNMP:

Trip: Occurs when a sensor value goes above a high trip threshold or below a low trip
threshold.

Clear: Occurs when a sensor already in the Tripped or Unplugged state goes back into its
normal range.

Unplugged: Occurs when a sensor with an alarm set loses contact with the main unit due
to the sensor being physically unplugged or another communications error.


Alarms can be added for each internal device or external sensor displayed on the Alarms page.
An alarm is added by pressing the “Add New Alarm” button and selecting the sensor value to be
monitored from a drop down menu.

Alarm Removal

To remove an alarm, select “REMOVE ALARM” from the sensor type drop-down menu then click
the “Save Changes” button.


Thresholds

The user must set a trip threshold and type for each alarm that is added to the Alarms page. The
threshold type is chosen as “Trips if” either “Above” or “Below” from a drop down menu when the
alarm is created. The threshold value is typed into a data window when the alarm is created.

Alarm

Type

Alarm

Threshold

Alert

Options