Dip switch setup – Hypertherm SensorOHC User Manual

Page 21

Advertising
background image

Section 3: Installation and Set Up

17

DIP Switch Setup

SW1 SW2 SW3

Sensor Cable Length

on

on

on

cable length = 500 mm

off

on

on

cable length = 800 mm

on

off

on

cable length = 900 mm

off

off

on

cable length = 1000 mm *

on

on

off

cable length = 1200 mm

off

on

off

cable length = 1500 mm


SW4

In Position 0utput in Manual Mode

off

Normal - active output near height set point*

on

Forced active - always active in Manual Mode


SW5 SW6 Sensitivity & Loop Gain
off

off Sensitivity lowest - Lowest Gain Most Stable / use for high speed lifters ( > 3000 mm/min )*

on

off Sensitivity medium low

off

on Sensitivity medium high

on

on Sensitivity highest - Highest Gain Least Stable / use for low speed lifters ( < 750 mm/min )


SW7 SW8 Max Motor Current
off

off

Current lowest = 2.0 Amp 50W

on

off

Current medium low = 3.0 Amps 75W

off

on

Current medium high = 4.0 Amps 100W

on

on

Current highest = 6.0 Amps 150W*


* Indicates setting as shipped.

NOTE: The RJ45 connector under the calibration panel is not a network connection. It is a proprietary
connector and is for the use of authorized service personnel only.