Owner’s manual, Troubleshooting – Desa B600D User Manual

Page 7

Advertising
background image

7

099507

OWNER’S MANUAL

OBSERVED PROBLEM

WARNING: Never service heater while it is plugged in, operating, or

hot. Severe burns and electrical shock can occur. Only a qualified service
person should service and repair heater.

TROUBLESHOOTING

Motor does not start when heater is plugged
in and thermostat setting is higher than
surrounding air temperature

1. No power or low voltage at heater due

to:
A) Damaged power cord or extension cord
B) Wrong size extension cord
C) Heater plugged into outlet with volt-
age lower than 120 volt

2. Loose electrical connections
3. Motor overload protector tripped due to:

A) Dirty fan
B) Debris pulled into fan area by fan
C) Binding pump
D) Low voltage

4. Flame-out control not reset

5. Damaged flame-out control
6. Damaged power relay
7. Damaged thermostat
8. Binding pump

1. A) Check condition of power cord or

ex tension cord. Repair or replace
damaged

B) Use extension cord with proper wire

size (see To Start Heater, page 5)

C) Make sure heater is plugged into 120

volt/60 hertz outlet

2. Check connections. Tighten if loose
3. A) See Fan Blades and Air Deflectors,

page 10

B) Remove debris from fan and fan

guard area

C) Turn fan by hand. If fan is hard to

turn, see Pump, page 11

D) See steps B and C under item 1 above

Note:

Be sure to reset motor overload

protector by pressing reset button on top
of motor.

4. Press and release flame-out control re-

set button. See Figure 4, page 5 for but-
ton location

5. Replace flame-out control
6. Replace power relay
7. Replace thermostat
8. Turn fan by hand. If fan is hard to turn,

see Pump, page 11

POSSIBLE CAUSE

REMEDY

Continued

www.desatech.com

Note:

For additional help, visit DESA

International’s Technical Service web
site at

www.desatech.com

.