Infloor Thermostat 29050 V1 User Manual

Installation, Quick setup, Additional setups

Advertising
background image

5

sensor

2. Installation

Remove the Thermostat Face

1. Remove the thermostat Front Module

from the Power Module by opening the door

and loosening the screw.

2. Pull outward near the bottom on the

Front Module and lift off.

Prepare the Wiring

1. Find a location for your thermostat. It

is suitable for indoor use only, on insulated

or uninsulated walls. Locate it about 4

1

2

feet to 5 feet above the floor on an

inside wall. Make sure it is well ventilated and not located in a confined space

such as a small closet or cabinet. Avoid placing it near other heat sources such

as hot-water piping, heat duct, wall-mount lighting, and direct sunlight to help

prevent adversely affecting the thermostat.

2. Turn off the power to the floor warming system at the main circuit panel

before doing any electrical work.

3. A qualified electrician should run a dedicated circuit from the main circuit

panel to the thermostat location.

4. If a dedicated circuit is not possible, you may tap from another circuit in the

room. Make sure there is enough load capacity (amps) to handle the addition

of your floor warming system, and that it is NOT wired in series with any other

device, including other GFCIs.

5. The circuit breaker in the main circuit panel should be 15 amps maximum

29050V1 Programmable Thermostat

Owner’s Manual

Your new Infloor Pro thermostat is designed to control the voltage to

either a 120VAC or 240VAC resistive floor warming system.
Please follow this manual for complete installation and operation instructions.

If you have any questions or comments, try calling Technical Support at

800 608-0562.

CAUTION

: Make sure you are qualified and are familiar with house wiring.

This is a line voltage device that could cause serious injury or damage if

improperly installed.

Connect Wires

1. Match and connect the two

wires marked “LINE1” and

“LINE2” to the power supply wires

using the wire nuts provided.

2. Gently tug on the wires to make

sure they are secure, otherwise

a

wire could loosen and cause

failure.

3. Overwrap the wire nuts with

electrical tape to better secure

them to the wires.

4. Match and connect the two

wires marked “LOAD1” and

“LOAD2” to the floor warming

system lead wires and secure

these wires the same way.

5. Connect the house ground wire

to the green or bare lead wire(s) of

your floor warming system.

6. Insert the ends of the floor

sensor wire into the “SENSOR”

terminals (1 and 2) and tighten

the screws. There is no polarity,

so it does not matter which wire

end goes into which terminal.

CAUTION:

Before continuing,

make sure your power supply

voltage matches the voltage rating

of your floor warming system.

Connecting 240V to a 120V floor

warming system will cause overheating and damage to the system and may

damage the control, other wiring, floor coverings, etc.

Remote Control

1. If you want to connect your thermostat to a remote control device, such as

a home automation system, first make sure that the remote device has a “dry

contact” output (an un-energized switch, such as the contacts on a relay). Many

home automation systems come with such an output that opens or closes at

specified times.

2. Pull 2-conductor wire, size 18- to 24-gage, through the wall from the remote

device, into this electrical box.

3. Connect the wire ends into the “SETBACK” terminals (5 and 6) and tighten

the screws (no polarity).

Infloor 29053V1 Relays

1. If you want to use your thermostat to drive a 29053V1 Relay(s) (ask your dealer

about this convenient way to control larger systems with one thermostat), first

read and follow the instructions for the Infloor Relay thoroughly.

2. Pull 2-conductor wire, size 18- to 24-gage, through the wall from the Infloor

Relay, into this electrical box. This wire may be up to 100 feet (30 m) in length

from the thermostat to the last Infloor Relay installed.

3. Connect the wire ends into the “RELOUT” terminals (3 and 4) and tighten the

screws(Observe polarity of the wires when connecting to the Infloor 29053V1 Relay).

Mount the Thermostat

1. Carefully fold and press the wires

back into the electrical box. Do not use

the thermostat to push them in, as this

may cause connections to loosen and

possible failure.

2. Secure the thermostat Power Module

into the box with the mounting screws

provided.

3. Carefully snap the Front Module onto

the Power Module.

4. Tighten the screw.

5. Switch on the power at the main circuit

panel.

3. Press the HOLD/RETURN button or wait 15 seconds and the thermostat will

return to the normal operating mode, saving your selection. The thermostat

will now display a P1, P2, P3, or P4 at the bottom right.

3. Quick Setup

On/Off Switch

Your thermostat should be turned off when it

is first installed. The display will show OFF and

the time and day.

1. Slide the on/off switch to the upper position,

turning the thermostat on. The display will

show the time and day, temperatures, and other

information.

2. To turn the thermostat off anytime, slide the

on/off switch to the lower position. No heating

will occur and all programming is retained.

Change Format Between °F / 12-hour and °C / 24-hour

Your thermostat is factory set to operate in either °F / 12 hour format or °C /

24 hour (military time) format. If needed, you may change this at any time as

follows:

1. Press the OPTIONS button and hold for 1 second. An °F and

12h will show on the display.

2. Press the down or up button to toggle to °C and 24h.

3. Press the HOLD/RETURN button to return to the normal

operating mode.

Set the Current Time and Day

1. Press the DAY/TIME button and hold for 1 second. The hour should be

blinking.

2. Press the down or up button to adjust the hour.

3. Press the DAY/TIME button briefly. The minutes should be

blinking.

4. Press the down or up button to adjust the minutes.

5. Press the DAY/TIME button briefly. The day should be blinking.

6. Press the down or up button to adjust the day.

7. Press the HOLD/RETURN button or wait 15 seconds and the

thermostat will return to the normal operating mode, saving your settings.

MO

SET TEMP

FLOOR

CYCLE

M

A

°F

1-4

Customized Program Schedule (User)

To customize the program shedule to meet your needs, follow

these steps:

1. Press the PROGRAM button and hold for 1 second. Pro and

U1, P1, P2, P3, or P4 will show on the display.

2. Press the down or up button to select U1.

3. Press the PROGRAM button briefly. CYCLE 1 and MO through

FR will show on the display. The hour should be blinking.

4. Press the down or up button to adjust the hour.

5. Press the PROGRAM button briefly. The minutes should be

blinking.

6. Press the down or up button to adjust the minutes.

7. Press the PROGRAM button briefly. The setpoint temperature

should be blinking.

8. Press the down or up button to adjust the setpoint temperature.

Note: A good rule of thumb is to adjust this about 5 to 8°F (3 to 5 °C)

lower during cycles when you are away to help reduce energy use. If you

set the “away” cycles too low, it will take much longer to raise the

temperature again and may result in unsatisfying performance.

Note: Some wood and laminate floor manufacturers recommend a

maximum of 82 to 84°F (27° to 28°C). Check with manufacturer.

9. Press the PROGRAM button briefly to move to the next cycle number.

10. Repeat Steps 3 through 7 to adjust the remaining cycle times and setpoint

temperatures MO through FR, and for the other days of the week.

11. When you finish, or at any time during these adjustments, press the

HOLD/RETURN button or wait 30 seconds and the thermostat will return to the

normal operating mode. Your adjustments will be saved.

Note: The display in normal operating mode will not show a “U1” indicating

“User” schedule. Also, all schedule adjustments are saved in memory and

will not be lost during power failure.

Note: If you only want to use two cycles during a day, clear the other cycles by

reducing their temperature below 40°F (4.5°C) to show (---).

To use these cycles again, adjust their time and temperature.

from

power

supply

on/off

MO

M

A

SET TEMP

LIMIT

FLOOR

°F

MO

°C

AIR

SET TEMP

SET BACK

LIMIT

FLOOR

USAGE

CYCLE

M

A

M

P

M

A

M

P

°C

°F

°C

°F

TUWE THFR SASU

HOLD

GFCI

TRIP

HEATING

°F

P1

P2

P3

P4

LOCK

MO

M

A

HEATING

MO

SET TEMP

CYCLE

M

A

°F

HOLD

USAGE

MO

CYCLE

M

A

°F

TUWE THFR

MO

CYCLE

M

A

°F

SET BACK

FLOOR

FLOOR

MO

CYCLE

M

A

°F

FLOOR

Use the Factory Programmed “User” Schedule

If you want to begin using your thermostat now without making any changes to

the factory set programming schedule, you may skip to section “5 Operation”.

It will operate in the “User” Schedule (U1), pre-programmed as follows, and

can be customized later to your needs (see section “4 Additional Setups”):

4. Additional Setups

Lifestyle Program Schedules (Presets)

There are convenient schedules already set up to meet typical lifestyles. If you

see a schedule P1 through P4 you like, select one as follows:

1. Press the PROGRAM button and hold for 1 second. Pro and

U1, P1, P2, P3, or P4 will show on the display.

2. Press the down or up button briefly to select P1, P2, P3, or P4.

These schedules are not able to be modified, and are as follows:

MO

M

A

SET TEMP

LIMIT

FLOOR

°F

MO

°C

AIR

SET TEMP

SET BACK

LIMIT

FLOOR

USAGE

CYCLE

M

A

M

P

M

A

M

P

°C

°F

°C

°F

TUWE THFR SASU

HOLD

GFCI

TRIP

HEATING

°F

P1

P2

P3

P4

LOCK

MO

M

A

HEATING

MO

SET TEMP

CYCLE

M

A

°F

HOLD

USAGE

MO

CYCLE

M

A

°F

TUWE THFR

MO

CYCLE

M

A

°F

SET BACK

FLOOR

FLOOR

MO

CYCLE

M

A

°F

FLOOR

MO

M

A

MO

°C

AIR

SET TEMP

SET BACK

LIMIT

FLOOR

USAGE

CYCLE

M

A

M

P

M

A

M

P

°C

°F

°C

°F

TUWE THFR SASU

HOLD

GFCI

TRIP

HEATING

°F

P1

P2

P3

P4

LOCK

MO

CYCLE

M

A

°F

TUWE THFR

MO

M

A

SET TEMP

LIMIT

FLOOR

°F

MO

°C

AIR

SET TEMP

SET BACK

LIMIT

FLOOR

USAGE

CYCLE

M

A

M

P

M

A

M

P

°C

°F

°C

°F

TUWE THFR SASU

HOLD

GFCI

TRIP

HEATING

°F

P1

P2

P3

P4

LOCK

MO

M

A

HEATING

MO

SET TEMP

CYCLE

M

A

°F

HOLD

USAGE

MO

CYCLE

M

A

°F

TUWE THFR

MO

CYCLE

M

A

°F

SET BACK

FLOOR

FLOOR

MO

CYCLE

M

A

°F

FLOOR

to

floor

warming

system

1. Preparation

1. Unpack your thermostat and make sure everything is in good condition:

Thermostat

Floor sensor

Small screwdriver

Mounting screws

Wire nuts for wiring connections

If any parts are missing or damaged, contact the store where you purchased

this thermostat. Do not install a damaged part.

2. Gather the following tools and supplies:

•Phillips screwdriver, hole saw

•Wire strippers, “fish tape”, other electrical tools

•Electrical box for thermostat:

a. If you are connecting to power leads from only 1 or 2 floor warming

systems, you may use a single-gang, 3

1

2

inch deep box.

b. If you are connecting to power leads from 3 floor warming systems,

use a 4x4x2

1

8

inch or deeper box (not a 2-gang box) when your wall studs

are still exposed. Install a single-gang “mud-ring” cover on the box before

installing drywall materials.

c. For more than 3 floor warming systems or other layouts, you may need

to install a junction box to connect the power leads together. Then use

house wire to connect between the junction box and the thermostat

electrical box. See the installation instructions for your floor warming

system for more information.

ALWAYS: Wire all circuits as Class 1, Electric Light and Power Circuits.

ALWAYS: Wire all circuits with insulation rated 600V minimum.

ALWAYS: Mount this control only to a grounded metallic box or a

nonmetallic box.

ALWAYS: Use power supply wires suitable for at least 90°C.

CAUTION: High voltage – disconnect power supply before servicing.

for a floor warming system totaling 12 amps or less. For larger systems up

to 15 amps, use a 20 amp maximum circuit breaker. Never exceed 15 amps

on this thermostat. You may consider using an arc-fault (AFCI) type circuit

breaker for additional protection.

6. Pull the power supply wiring into this box, leaving about 6 inches of wire.

7. Pull the floor sensor wire and the power lead wires from your floor warming

system up the wall, into this box. Refer to your floor warming system

installation instructions for placement of the floor sensor tip into the floor area.

Note: The sensor wires should not be run in the same conduit as line voltage

wires to avoid possible interference. If the sensor lead wires are not long

enough, they may be extended an additional 15 feet (4.5 m) using minimum

20-gage 2-conductor wire or up to 50 feet (15 m) using shielded wire.

8. Mount the electrical box.

power

module

front

module

MO

M

A

SET TEMP

LIMIT

FLOOR

°F

MO

°C

AIR

SET TEMP

SET BACK

LIMIT

FLOOR

USAGE

CYCLE

M

A

M

P

M

A

M

P

°C

°F

°C

°F

TUWE THFR SASU

HOLD

GFCI

TRIP

HEATING

°F

P1

P2

P3

P4

LOCK

MO

M

A

HEATING

MO

SET TEMP

CYCLE

M

A

°F

HOLD

USAGE

MO

CYCLE

M

A

°F

TUWE THFR

MO

CYCLE

M

A

°F

SET BACK

FLOOR

FLOOR

MO

CYCLE

M

A

°F

FLOOR

Cycle

1

2

3

4

Mon-Fri

6:00 am

8:00 am

5:00 pm

10:00 pm

82 F

74 F

82 F

74 F

Saturday

7:00 am

9:00 am

5:00 pm

11:00 pm

82 F

74 F

82 F

74 F

Sunday

7:00 am

9:00 am

5:00 pm

11:00 pm

82 F

74 F

82 F

74 F

U1 (User changeable)

82 F

82 F

74 F

74 F

Note: Air Sensing mode default temperatures are 70F and 62F.

Cycle

1

2

3

4

Mon-Fri

5:00 am

7:00 am

5:00 pm

10:00 pm

82 F

74 F

82 F

74 F

Saturday

5:00 am

9:00 am

5:00 pm

10:00 pm

82 F

74 F

82 F

74 F

Sunday

5:00 am

9:00 am

5:00 pm

10:00 pm

82 F

74 F

82 F

74 F

P1 (Early Riser)

Note: Air Sensing mode default temperatures are 70F and 62F.

Cycle

1

2

3

4

Mon-Fri

5:00 am

8:00 am

6:00 pm

11:00 pm

82 F

74 F

82 F

74 F

Saturday

6:00 am

9:00 am

5:00 pm

11:00 pm

82 F

74 F

82 F

74 F

Sunday

6:00 am

9:00 am

5:00 pm

11:00 pm

82 F

74 F

82 F

74 F

P2 (Longer Day)

Note: Air Sensing mode default temperatures are 70F and 62F.

Cycle

1

2

3

4

Mon-Fri

6:00 am

9:00 am

6:00 pm

10:00 pm

75 F

70 F

75 F

70 F

Saturday

7:00 am

10:00 am

6:00 pm

10:00 pm

75 F

70 F

75 F

70 F

Sunday

7:00 am

10:00 am

6:00 pm

10:00 pm

75 F

70 F

75 F

70 F

P4 (Take the chill off)

Note: Air Sensing mode default temperatures are 65F and 60F.

Cycle

1

2

3

4

Mon-Fri

6:00 am

8:00 am

6:00 pm

10:00 pm

82 F

79 F

82 F

75 F

Saturday

6:00 am

9:00 am

6:00 pm

10:00 pm

82 F

79 F

82 F

75 F

Sunday

6:00 am

9:00 am

6:00 pm

10:00 pm

82 F

79 F

82 F

75 F

P3 (At home during the day)

Note: Air Sensing mode default temperatures are 70F, 67F, and 62F.

Example

Cycle

1

2

3

4

Mon-Fri

--:--

7:30 am

6:00 pm

--:--

-- F

72 F

80 F

-- F

80 F

80 F

72 F

NOTE to contractors: After installing the thermostat, be sure to:

a. Do a Quick Setup (section 3),

b. Temporarily override the setpoint temperature to make sure it is

heating for a few minutes (section 5),

c. Test the GFCI (section 5).

P

Advertising