Infloor Autofill and Backflow 31070, 31071 User Manual

Pre-adjustable filling units & backflow preventer

Advertising
background image

Pre-adjustable filling units

& backflow preventer

Part # 31070 - 31071

cert. n° 0003

ISO 9001

01061/04 NA

Function

The automatic filling unit is a device consisting of a pressure
reducing valve with compensating seat, an inlet filter, a shut-off
valve and a check valve.

It is installed on the water inlet piping in sealed heating systems,
and its main function is to maintain the pressure of the system
stable at a set value, automatically filling up with water as required.
This product has the characteristic of being pre-adjustable,
which means that it can be adjusted at the required pressure
value before the system charging phase.

After installation, during the filling or topping-off phase, the water

feed will stop when the set pressure is reached.

A pre-assembled version is also available, complete with upstream
backflow preventer.

C

US

ASSE 1012

Product range

Code 31071 Filling unit with pressure gauge and pressure setting indicator

Size 1/2”

Code 31070 Charging unit complete with backflow preventer series

Size 1/2”

Technical specification

Filling unit

Material: Body: brass

Cover:

PA 66 GF 30

Seals:

NBR

Maximum Working Pressure: 230 psi (16 bar) Pressure
setting range: 3÷60 psi (0.2÷4 bar) Factory setting:
15 psi (1.035 bar)

Indicator accuracy: ±2 psi (±0.15 bar) Maximum
Working Temperature: 150°F (65°C)

Connection: Inlet: 1/2” NPT Male with union tailpiece

Outlet:

1/2” NPT Female

Backflow preventer

Material: Body: brass

Check valve:

PSU

Check valve stem:

brass

Diaphragm:

EPDM

Seals:

EPDM

Maximum working pressure: 175 psi (12 bar) Maximum
working temperature: 210°F (99°C) Medium: water

Certified to: CSA B64.3 and ASSE 1012

Connections: 1/2”-3/4” NPT female with union

Advertising