Installation

1. Filling unit can be installed in either horizontal or vertical position.
It is, however, vital that the unit is not installed upside down.

2. The special method of mechanical pre-adjustment with pressure
setting indicator makes it possible to set the unit to the required value
in the system before the beginning of the filling phase.

3. The unit is normally set at a pressure not less than that obtained by
adding the hydrostatic pressure and 4 psi (0,3 bar).

4. During filling, the internal mechanism will automatically regulate the
pressure until it reaches the required value, without the need to
oversee the filling operation
itself. This prevents the system being
charged to a higher pressure than required.

5. Given the pre-calibrating function, the presence of the downstream
pressure gauge is not essential.

6. When the system is filled, the shut-off valve can be closed. In order
to restore the automatic topping-off condition, merely re-open the valve.
The pressure in the system will gradually return to the set pressure.

Maintenance

For cleaning, inspection or
replacement of the entire

2

cartridge, proceed as follows:

1. Isolate the unit.

2. Open the lower control

knob.

3. Unscrew

the

adjusting

3

screw until it stops.

4. Remove the upper cover.

5. Extract the cartridge using

pliers.

6. The

entire

unit,

after

inspection,

can

be

reassembled or replaced

5

using a spare cartridge.

7. Re-adjust the equipment.

Backflow preventer

Flow rate graph

The backflow preventer with atmospheric vent is designed to
protect drinking water systems from the return, caused by back
siphonage or backpressure, of contaminated fluids.

The Caleffi 573 series has been specifically certified to standards
CSA B64.3 and ASSE 1012.