Installation, Continued, Mantel clearances – Desa CCL3924PRA User Manual

Page 10

Advertising
background image

www.desatech.com

111161-01H

10

INSTALLATION

Continued

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace

If Using Mantel

You must have noncombustible material(s) above

the fireplace opening. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2" thick. With sheet metal, you must have non-

combustible material behind it. Noncombustible

material must extend at least 8" up (for all models).

If noncombustible material is less than 12", you

must install the fireplace hood accessory (24" and

30" models only). Even if noncombustible material

is more than 12", you may need the hood acces-

sory to deflect heat away from your mantel shelf.

See Figure 5 and Figures 6 and 7 on page 9 for

minimum clearances.
IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 11.

Noncombustible Requirements for
Material

Safe Installation

Distance (A)
1" or more

Noncombustible material

okay.

Between 8"

Install fireplace hood

and 1"

accessory (GA6050,

GA605 or GA6053 see

Accessories, page 34).

Less than 8"

Noncombustible material

must be extended to at

least 8". See Between 8"

and 1", above. If you

cannot extend material,

you must operate heater

with flue damper open.

Heat Resistant
Material

(A)

MANTEL CLEARANCES

In addition to meeting noncombustible material

clearances, you must also meet required clearances

between fireplace opening and mantel shelf. If

you do not meet the clearances listed below, you

will need a hood.
Determining Minimum Mantel Clearances

If you meet minimum clearance between mantel

shelf and top of fireplace opening, a hood is not

required (see Figure 6).
Determining Minimum Mantel Clearances
When Using a Hood

If minimum clearances in Figure 6 are not met, you

must have a hood. When using a hood there are

still certain minimum mantel clearances required.

Follow minimum clearances shown in Figure 7,

page 11, when using hood.

NOTICE: Surface temperatures

of adjacent walls and mantels be-

come hot during operation. Walls

and mantels above the firebox

may become hot to the touch.

If installed properly, these tem-

peratures meet the requirements

of the national product standard.

Follow all minimum clearances

shown in this manual.

Figure 6 - Minimum Mantel Clearances

Without Using Hood

Minimum

Noncombustible

Material

Minimum

Noncombustible

Material Height

Distances to

Underside of

Mantel

Top of Fireplace

Opening

Underside

of Mantel

Shelf

Mantel Shelf

12"
8"

(A)

18"
8"

20"
14"

22"
17"

24"
20"

All minimum

distances

are in inches

Log Set
24"/30"

Models
18" Model

2

1/2

"

6"

8"

10"

Advertising
This manual is related to the following products: