Ventilation, Operation, Installation – Desa Air Conditioner User Manual

Page 5

Advertising
background image

www.desatech.com

113893-01B

5

1. Provide propane supply system (see Propane

Supply, page 4).

2. Connect fuel gas connector fitting on

hose/regulator assembly to propane tank(s).

Turn counterclockwise into threads on

tank valve. Tighten firmly using wrench.

IMPORTANT:

Tighten regulator with vent

pointing down. Pointing vent down protects

regulator from weather damage.

3. Connect hose to inlet connector. Tighten

firmly using a wrench. IMPORTANT: Extra

hose or piping may be used if needed. Install

extra hose or piping between hose/regulator

assembly and propane tank. You must use the

regulator supplied with heater.

4. Open propane supply valve on propane tank(s)

slowly. Note: If not opened slowly, excess-

flow check valve on propane tank may stop

gas flow. If this happens, close propane supply

valve and open again slowly.

5. Check all connections for leaks.
6. Close propane supply valve.

INSTALLATION

Continued

Figure 4 - Hose and Inlet Connector

(Heater may vary from illustration)

Hose

Inlet Connector

Figure 3 - Regulator With Vent Pointing

Down

Propane
Tank

Hose

Regulator

Vent
(pointing
down)

Fuel Gas
Connector

Supply
Valve

VENTILATION

WARNING: Follow the mini-

mum fresh, outside air ventila-

tion requirements. If proper

fresh, outside air ventilation is

not provided, carbon monoxide

poisoning can occur. Provide

proper fresh, outside air ventila-

tion before running heater.

Provide a fresh air opening of at least three square

feet for each 100,000 Btu/Hr (105,500 k/j) rat-

ing. Provide extra fresh air if more heaters are

being used.

OPERATION

WARNING: Review and un-

derstand the warnings in the

Safety Information section, page

2. They are needed to safely op-

erate this heater. Follow all local

codes when using this heater.

TO START HEATER

1. Follow all installation, ventilation and safety

information.

2. Locate heater on stable and level surface.

Make sure strong drafts do not blow into front

or rear of heater.

3. Plug power cord of heater into a three-prong,

grounded extension cord. Extension cord must

be at least six feet (1.83 m) long, UL/CSA

listed and of a proper size.

Extension Cord Size Requirement

Up to 100 feet (30.5 m) long, use 16 AWG

rated cord.

101 to 200 feet (30.78 to 61 m) long, use 14

AWG rated cord.

4. Plug extension cord into a 120 volt/60 hertz,

three-hole, grounded outlet. Motor will start.

Fan will turn, forcing air out front of heater.

5. Open propane supply valve on propane

tank(s) slowly. Note: If not opened slowly,

excess-flow check valve on propane tank will

stop gas flow. You may hear a click from the

excess-flow check valve closing. If this hap-

pens, reset the excess-flow check valve by

closing propane supply valve and open again

slowly.

Advertising