INSTALLING

Continued

Continued

Test Pressures Equal To or Less Than 1/2 PSIG

1. Close manual shutoff valve (see Figure 20).
2. Pressurize supply piping system by either using compressed air or opening

propane/LP supply tank valve.

3. Check all joints from propane/LP supply tank to manual shutoff valve (see

Figure 21). Apply mixture of liquid soap and water to gas joints. Bubbles
forming show a leak.

4. Correct all leaks at once.

Pressure Testing Fireplace Gas Connections

1. Open manual shutoff valve (see Figure 20).
2. Open propane/LP supply tank valve.
3. Make sure control knob of fireplace is in the OFF position.
4. Check all joints from manual shutoff valve to thermostat gas valve (see Figure

21). Apply mixture of liquid soap and water to gas joints. Bubbles forming
show a leak.

5. Correct all leaks at once.
6. Light fireplace (see Operating Fireplace, pages 21 through 23 [Thermostat-

controlled models] or pages 23 through 25 [Manually-controlled models]).
Check all other internal joints for leaks.

7. Turn off fireplace (see To Turn Off Gas to Appliance, page 23, [Thermostat-

controlled models] or page 25 [Manually-controlled models]).

Figure 20 - Manual Shutoff Valve

ON

POSITION

OFF

POSITION

Open

Closed

Manual
Shutoff
Valve