Product specifications – Nortec MH Series User Manual

Page 53

Advertising
background image

MH Series | 49

Product Specifications

Table 5: Technical Data

MHB

Flow

MHTC

Flow

MHB

Reflow

MHTC

Reflow

Control

Humidistat

Total controller

Control MHB Total controller

Control supply charge

120 vac /

60 hz

120 vac /

60 hz

120 vac /

60 hz

120 vac /

60 hz

Circulation pump supply voltage

---

---

120 vac/60 hz

Control signals

Potential free

contact of an

external

humidistat /

thermostat

0…5 vdc
1…5 vdc

0…10 vdc
2…10 vdc
0…16 vdc

3.2…16 vdc

0..20 ma
4..20 ma

Potential free

contact of an

external

humidistat /

thermostat

0…5 vdc
1…5 vdc

0…10 vdc
2…10 vdc
0…16 vdc

3.2…16 vdc

0..20 ma
4..20 ma

Control characteristics

On/off

Control step

On/off

Control step

Control accuracy

Control accuracy depends on air conditions, control distance, water

quality and the number of on/off cycles.

Max. Admissible air speed above
humidification boxes

3.8 m/s / 750 fpm (4.5 m/s / 885 fpm with 4” (100 mm) mist

eliminator, 5.5 m/s with 8” (200 mm) mist eliminator.

Water supply

R ¾” outside thread

Water drain

1.2 5" pvc (1.66" (42 mm) od) outside diameter of tube

Admissible water supply pressure

30-145 psi (2-10 bar)

Admissible water temperature

41-113ºf (5-45ºc)

Water quality

Tap water, reverse osmosis, softened or fully demineralized water.

Pressure drop

Typically 0.44 iwc @ 500 fpm, 90% rh

Admissible ambient temperature
(control unit)

34…104ºF

1…40ºC

34…104ºF

1…40ºC

34…104ºF

1…40ºC

34…104ºF

1…40ºC

Admissible ambient humidity (control
unit)

Max. 75% rh

Max. 75% rh

Max. 75% rh

Max. 75% rh

Fire classification of humidification
medium

Ul 900 class 1

Advertising