Technical Guide

E-BUS Adapter Board

5

Airfl ow Monitoring Station to VCM-X E-BUS or RNE Controller Wiring

Connecting to the VCM-X E-BUS or

RNE Controller

NOTE: Only the EBTRON

®

GTC116 series* or GreenTrol

TM

GA-200-N Module (with GF series Airfl ow Station)
of MODBUS transmitters are compatible with the
VCM-X E-BUS or RNE Controller.** No other series of
EBTRON

®

or GreenTrol

TM

transmitters will work for

this application.

The E-BUS Adapter Board attaches to the VCM-X E-BUS or RNE
Controller with an HSSC E-BUS cable (supplied separately). The
Adapter Board is used for connecting the EBTRON

®

or GreenTrol

TM

Airfl ow Measurement Digital Transmitter to the VCM-X E-BUS
or RNE Controller. You must wire the EBTRON

®

or GreenTrol

TM

Airfl ow Measurement Digital Transmitter to the Adapter Board as
shown in Figure 3.

NOTE: Up to 3 EBTRON

®

or GreenTrol

TM

Airfl ow

Measurement Digital Transmitters can be
attached to each Adapter Board.

*NOTE: When confi guring the GTC-116 Series, be sure to

set the Parity to “NO PARITY, 1 STOP BIT.”

**NOTE: With custom VCM-X / RNE software, Paragon Micro-

Trans

EQ

Airfl ow Stations can be used and would wire

into the E-BUS Adapter Board the same way. The
Paragon MODBUS ID must be set to 9 and the baud
rate must be set to 9600.

Figure 3: EBTRON

®

GTC116 Series and GreenTrol

TM

GA-200-N Series to VCM-X E-BUS or RNE Controller

Wiring (VCM-X E-BUS Controller Shown)

COMM

COMM

NET-

NET-

NET+

NET+

Airflow Measurement

Digital Transmitter Terminals

For Outdoor Air CFM

(Set Address Switch To 9)

Airflow Measurement

Digital Transmitter Terminals

For Return or Exhaust Air CFM

(Set Address Switch To 10)

Airflow Measurement

Digital Transmitter Terminals

For Supply Air CFM

(Set Address Switch To 11)

COMM

NET-

NET+

OE332-23E-VCMX-MOD

VCM-X E-BUS Controller

OE365-15-EBA

E-BUS Adapter Board

I2C DIGITAL

SENSOR

I2C

EXPANSION

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

WattMaster Label

#LB102033-01

AI1 AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

EMERGENCY SHUTDOWN

AI1 SET

AI1

THERM

THERM

4-20mA
0-10V

0-5V

ANALOG INPU

JUMPER

SETTINGS

HSSC Cable Connect To

HSSC E-BUS Port

Connect To

VCM-X or RNE E-BUS Port

WARNING!!

Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
To observe polarity could result in
damage to the boards.

Size Transformer For
Correct Total Load.
VCM-X E-BUS or RNE
Controller = 8 VA.
Power Terminal Block Not
Shown.

NOTE:

NOTE: One Or Both
Terminal Blocks Can be
Used.