E-BUS Modules and/or Sensors to VCB-X Controller Wiring

Figure 4: Multiple E-BUS Sensors Wiring to VCB-X Controller Using the E-BUS Adapter

Connecting Multiple E-BUS Modules

and/or Sensors to the VCB-X

Controller

If using multiple E-BUS Sensors or Modules, the E-BUS Adapter
Board can be used when there are not enough available E-BUS ports
on the Unit Controller.

Up to (3) E-BUS Modules or Sensors can be connected to the E-BUS
Adapter Board(s) MODBUS E-BUS ports. The VCB-X Control-
ler connects to the fourth MODBUS E-BUS port on the E-BUS
Adapter Board.

See Figure 4 for wiring details when connecting multiple E-BUS
modules and/or sensors to the VCB-X Controller.

OE265-15-A Horizontal

Temperature

& Humidity Sensor

EBC E-BUS Cable with

Jack Connection

NOTE: Connect both
Sensors to the E-BUS
Adapter’s Modular
E-BUS Ports Using The
Provided EBC E-BUS
Cables.

24 VAC POWER

ONLY

WARNING!

POLARITY MUST

BE OBSERVED

OR THE

CONTROLLER

WILL BE

DAMAGED

AO2

AO3

TR1

= SC

= DIGITAL CO

TRIAC OUTPUT

LED N

M

NORMAL

SAT FAIL

OAT FAIL

SPC FAIL

MECH COOL FAIL

MECH HEAT FAIL

FAN PROOF FAIL

DIRTY FILTER

EMERGENCY SHUTDOWN

LOW SAT

1

HIGH SAT

2

CONT. TEMP COOL FAIL

3

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

OUTPUT FORCE ACTIVE

0

6

WattMaster Label

#LB102093-01-A

Rev.: 1C

E-BUS

EXPANSION

E-BUS

EXPANSION

24 VAC

INPUT

=

37X04

1.2

1.6

<PC>

4 3 2 1

3M

OE256-07 Duct Mounted

E-BUS CO Sensor

2

37X04

1.2

1.6

<PC>

4 3 2 1

3M

EBC E-BUS Cable

with Jack

Connection

OE365-15-EBA

E-BUS Adapter Board

OE335-23-VCBX

VCB-X Controller

NOTE: Connect
the VCB-X
Controller To The
E-BUS Adapter’s
Modular E-BUS
Port.

24VAC

GND

Line

Voltage

WARNING!!

Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
To observe polarity could result in
damage to the boards.

Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA