Technical Guide

E-BUS Adapter Board

7

Airfl ow Monitoring Station to VCB-X Controller Wiring

Connecting to the VCB-X Controller

NOTE: Only the EBTRON

®

GTC116 series. GreenTrol

TM

GA-200-N Module (with GF series Airfl ow Station) or
Paragon MicroTrans

EQ

series of MODBUS transmit-

ters are compatible with the VCB-X Controller. No
other series of EBTRON

®

, GreenTrol

TM

, or Paragon

transmitters will work for this application. Contact
WattMaster Controls for information on other
airfl ow station options.

The E-BUS Adapter Board attaches to the VCB-X Controller with
an EBC E-BUS cable (supplied separately). The Adapter Board
is used for connecting the EBTRON

®

or GreenTrol

TM

, or Paragon

Airfl ow Measurement Digital Transmitter to the VCB-X Control
System. You must wire the EBTRON

®

, GreenTrol

TM

, or Paragon

Airfl ow Measurement Digital Transmitter to the Adapter Board as
shown in Figure 5.

NOTE: Up to 4 EBTRON

®

, GreenTrol

TM

, or Paragon

Airfl ow Measurement Digital Transmitters can be
attached to each Adapter Board.

NOTE: If using multiple E-BUS Sensors or Modules, the

E-BUS Hub (HZ-EBC-248 or MS000248) may be
required.

*NOTE: When confi guring the GTC-116 Series, be sure to set

the Parity to “NO PARITY, 1 STOP BIT.”

Figure 5: EBTRON

®

GTC116 Series, GreenTrol

TM

GA-200-N Series, and Paragon MicroTrans

EQ

Series Wiring

WARNING!!

Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
To observe polarity could result in
damage to the boards.

COMM

COMM

COMM

NET-

NET-

NET-

NET+

NET+

NET+

Airflow Measurement

Digital Transmitter Terminals

For Outdoor Air CFM

(Set Address Switch To 9)

Airflow Measurement

Digital Transmitter Terminals

For Return Air CFM

(Set Address Switch To 10)

Airflow Measurement

Digital Transmitter Terminals

For Supply Air CFM

(Set Address Switch To 11)

COMM

NET-

NET+

Airflow Measurement

Digital Transmitter Terminals

For Exhaust Air CFM

(Set Address Switch To 12)

24 VAC POWER

ONLY

WARNING!

POLARITY MUST

BE OBSERVED

OR THE

CONTROLLER

WILL BE

DAMAGED

AO2

AO3

TR1

= SC

= DIGITAL CO

TRIAC OUTPUT

LED N

M

NORMAL

SAT FAIL

OAT FAIL

SPC FAIL

MECH COOL FAIL

MECH HEAT FAIL

FAN PROOF FAIL

DIRTY FILTER

EMERGENCY SHUTDOWN

LOW SAT

1

HIGH SAT

2

CONT. TEMP COOL FAIL

3

CONT. TEMP HEAT FAIL

4

4

PUSH BUTTON OVR

1

5

OUTPUT FORCE ACTIVE

0

6

WattMaster Label

#LB102093-01-A

Rev.: 1C

E-BUS

EXPANSION

E-BUS

EXPANSION

24 VAC

INPUT

=

24VAC

GND

Line
Voltage

Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA

E-BUS Cable

(EBC Cable)

OE335-23E-VCBX

VCB-X Controller

OE365-15-EBA

E-BUS Adapter Board

NOTE: One Or Both
Terminal Blocks Can be
Used.

Revised: 10/23/13