Water source heat pump module, Sequence of operation – Orion System Water Source Heat Pump Module Tulsa User Manual

Page 12

Advertising
background image

Water Source Heat Pump Module

Technical Guide

12

Sequence of Operation

Stand-Alone Input Commands

Compressor On/Off

A 24 volt signal to Binary Inputs #1-4 initiates each Compressor’s On
function. The source for this signal would typically come from Y1 to
Y4 calls from the thermostat.

Heat Enable On/Off

A 24 volt signal on this input indicates the unit is in the Heating Mode.
Typically, the source for this signal is the “O” call from the thermo-
stat.

Water Proof of Flow System On/Off

A 24 volt signal to Binary Inputs #6-7 indicates Water Proof of Flow
for each system.

Suction Pressure Analog Inputs

Sensors from Analog Inputs #1-4 correlate with the Suction Pressure of
each Compressor (250 PSI).

Leaving Water Temperature Thermistor Inputs

T1 correlates with Compressors A1 & A2 (RLY1 and RLY2). T2 cor-
relates with Compressors B1 & B2 (RLY3 and RLY4).

Input Commands (VCM-X WSHP or SA

Connection)

NOTE: When the term “ON” is used, it means there is either 24

VAC on the appropriate Binary Input or a call-to-run
signal is being received from the VCM-X WSHP or SA
Controller. When the term “OFF” is used, it means there
is either 0 VAC on the appropriate Binary Input or the
call-to-run signal from the VCM-X WSHP or SA has
been removed.

Compressor On/Off

Instead of a physical input signaling the Compressor On/Off function,
the VCM-X WSHP Controller or SA Controller communications drives
the Compressor On/Off function.

Heat Enable On/Off

As with the Compressor On/Off function, the VCM-X WSHP or SA
Controller communicates to the Module that it is in Heat Mode.

Advertising