Water source heat pump module, Troubleshooting – Orion System Water Source Heat Pump Module Tulsa User Manual

Page 16

Advertising
background image

Water Source Heat Pump Module

Technical Guide

16

OE275-01 Suction Pressure Transducer

Testing for R-22 & R-410A Refrigerant

The Evaporator Coil Temperature is calculated by converting the Suc-
tion Pressure to Temperature. The Suction Pressure is obtained by using
the OE275-01 Suction Pressure Transducer, which is connected into the
Suction Line of the Compressor.

Use the voltage column to check the Suction Pressure Transducer while
connected to the WSHP Module. Read voltage with a meter set on DC
volts. If the temperature/voltage or pressure/voltage readings do not
align closely with the chart, your Suction Pressure Transducer is prob-
ably defective and will need to be replaced.

See the OE275-01 Suction Pressure Transducer, Press pressures.ure,
Temperature, and Voltage Charts for R-22 and R-410A Refrigerant test-
ing (Tables 6 & 7). The charts show a temperature range from 20°F to
80°F. For troubleshooting purposes, the DC Voltage readings are also
listed with their corresponding temperatures and

Table 7: Coil Pressure/Voltage/Temp for OE275-01
Suction Pressure Transducers - R-410A Refrigerant

Troubleshooting

OE275-01 Suction Pressure Transducer Coil Pressure

– Temperature – Voltage Chart for R-410A Refrigerant

T

emperature

°F

Pressure

PSI

Signal

DC V

olts

T

emperature

°F

Pressure

PSI

Signal

DC V

olts

21.19

80.94

1.8

59.03

168.10

3.2

24.49

87.16

1.9

61.17

174.32

3.3

27.80

93.39

2.0

63.19

180.55

3.4

30.99

99.62

2.1

65.21

186.78

3.5

33.89

105.84

2.2

67.23

193.00

3.6

36.80

112.07

2.3

69.24

199.23

3.7

39.71

118.29

2.4

71.15

205.46

3.8

42.30

124.52

2.5

72.95

211.68

3.9

44.85

130.75

2.6

74.76

217.91

4.0

47.39

136.97

2.7

76.57

224.14

4.1

49.94

143.2

2.8

78.37

230.36

4.2

52.23

149.42

2.9

80.18

236.59

4.3

54.50

155.65

3.0

56.76

161.88

3.1

Table 6: Coil Pressure/Voltage/Temp for OE275-01
Suction Pressure Transducers - R-22 Refrigerant

OE275-01 Suction Pressure Transducer Coil Pressure

– Temperature – Voltage Chart for R-22 Refrigerant

T

emperature

°F

Pressure

PSI

Signal

DC V

olts

T

emperature

°F

Pressure

PSI

Signal

DC V

olts

20.00

31.13

1.0

55.32

93.39

2.0

20.00

37.36

1.1

58.86

99.62

2.1

20.46

43.58

1.2

62.13

105.84

2.2

25.71

49.80

1.3

65.27

112.07

2.3

30.84

56.03

1.4

68.42

118.29

2.4

35.41

62.26

1.5

71.39

124.52

2.5

39.98

68.49

1.6

75.20

130.75

2.6

44.00

74.71

1.7

77.00

136.97

2.7

48.00

80.94

1.8

79.80

143.20

2.8

51.78

87.16

1.9

80.00

149.42

2.9

Advertising