Water source heat pump module, Module overview, Technical guide 4 overview – Orion System Water Source Heat Pump Module Tulsa User Manual

Page 4: Features, Figure 1: water source heat pump module, Distribution module to e-bus interface

Advertising
background image

Water Source Heat Pump Module

Technical Guide

4

Overview

The Water Source Heat Pump Module monitors the compressors on an
AAON Water Source Heat Pump unit and can disable the compressors
based on low Suction Pressure, Leaving Water Temperature, and Water
Proof of Flow inputs. It also utilizes a Delay Timer to prevent the com-
pressors from turning on at the same time.

There are two water-only versions of the Water Source Heat Pump
Module—the OE334-23-WPM-A which uses R-410A refrigerant and
the OE334-23-WPM-22-A which uses R-22 refrigerant.

There are also three R-410-A glycol versions—the OE334-23-WPM-A20
which uses 20% glycol—the OE334-23-WPM-A25 which uses 25%
glycol and the OE334-23-WPM-A40 which uses 40% glycol.

The Water Source Heat Pump Module can be used stand-alone. It can
also

be connected

to the VCM-X WSHP Controller (OE332-23-VCMX-

WSHP-A) or SA Controller (OE332-23-SA) using the E-BUS Distribu-
tion Module (OE365-23-EBD). This allows the Water Source Heat Pump
Module to receive control data and alarms from the VCM-X WSHP or
SA Controller. Please note: The SA Controller only works with the
OE-334-WPM-A (410A version).

Module Overview

Figure 1: Water Source Heat Pump Module

The Water Source Heat Pump Module requires a 24 VAC power con-
nection with an appropriate VA rating.

Features

The Water Source Heat Pump Module provides the following:



Can be operated stand-alone or connected to a

VCM-X WSHP Controller or SA Controller using

the

E-BUS

Distribution Module to E-BUS interface



Capable of controlling digital compressors when

connected to the VCM-X WSHP Controller or SA

Controller



Monitors suction pressure, leaving water

temperature, and water proof of fl ow



Provides Delay Timer to prevent compressors

from turning on at the same time

NOTE: The Water Source Heat Pump Module contains no user-

serviceable parts. Contact qualifi ed technical personnel
if your Module is not operating correctly.

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

WattMaster Label

#LB102069-A

Rev.: 1B

E-BUS

Connector

E-BUS

Connector

+5V

PRES

GND

+24

VAC

GND

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

SUCTION
PRESSURE
TRANSDUCERS
#1 thru #4

COMP. 1 ENABLE
COMP. 2 ENABLE
COMP. 3 ENABLE

WSHP Protection Module

Orion No.: OE334-23-WPM

COMP. 4 ENABLE
HEAT ENABLE
H2O POF #1
H2O POF #2
COMMON

T 1

T 2

GND

LEAVING WATER TEMP 1

GROUND

LEAVING WATER TEMP 2

LED BLINK CODES

LED NAME

STATUS

OFF MODE

1

COOLING MODE

2

HEATING MODE

3

LED NAME

ALARM

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

WATER FLOW FAILURE

3

LOW LEAVING WATER TEMP.

4

LED NAME

PRES 1-4

SENSOR DETECTED

ON

NO SENSOR DETECTED

OFF

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

AO1

A2O

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. #2 ENABLE

COMP. #1 ENABLE

R1

R2

R3

R4

RC

RELAY COMMON

COMP. #3 ENABLE

COMP. #4 ENABLE

SYSTEM A - CNTRLR C2

SYSTEM B - CNTRLR C2

+5V

PRES

GND

NOT USED

DIGITAL COMP #1 THRU #4

NON-DIGITAL COMP #1 THRU #4

COPELAND CNTRLR P6
COPELAND CNTRLR P5

AAON No.: R90680

WattMaster Label

#LB102069-A

Rev.: 1F

E-BUS

Connector

E-BUS

Connector

+24

VAC

GND

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

COMP. A1 ENABLE
COMP. A2 ENABLE
COMP. B1 ENABLE

WSHP Module

Orion No.: OE334-23-WPM-A

AAON No.: R88350

www.aaon.com

www.orioncontrols.com

COMP. B2 ENABLE
HEAT ENABLE
WATER POF A
WATER POF B
COMMON

T 1

T 2

GND

LEAVING WATER TEMP A

GROUND

LEAVING WATER TEMP B

LED BLINK CODES

LED NAME

STATUS

OFF MODE

1

COOLING MODE

2

HEATING MODE

3

LED NAME

ALARM

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

WATER FLOW FAILURE

3

LOW LEAVING WATER TEMP.

4

LED NAME

PRES 1-4

SENSOR DETECTED

ON

NO SENSOR DETECTED

OFF

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

AO1

A2O

STAGE 1- COMP. A1/B1-

STAGE 2 - COMP. A2/B2

DIGITAL COMP. A1, A2, B1, B2

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5
RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO CNTLR C2 TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

LW: 36ºF HSP: 100 PSIG