Water source heat pump module, Installation & wiring, Technical guide – Orion System Water Source Heat Pump Module Tulsa User Manual

Page 5: Power supply, Environmental requirements, Mounting, Figure 2: water source heat pump module dimensions

Advertising
background image

Technical Guide

Water Source Heat Pump Module

5

Installation & Wiring

Power Supply

The Water Source Heat Pump Module requires a 24 VAC power con-
nection with an appropriate VA rating.

If you will be connecting the Water Source Heat Pump Module to the
VCM-X WSHP Controller or SA Controller, one of the most important
checks to make before powering up the system for the fi rst time is to
make sure that the VCM-X WSHP Controller or SA Controller is con-
fi gured properly for your application. Refer to the VCM-X Controller
Technical Guide
or SA Controller Technical Guide for more information.

WARNING: Observe polarity! All boards must be wired

GND-to-GND and 24 VAC-to-VAC. Failure to

observe polarity could result in damage to the

boards.

Environmental Requirements

The Water Source Heat Pump Module needs to be installed in an environ-
ment that can maintain a temperature range between -30°F and 150°F
and not exceed 90% RH levels (non-condensing).

Mounting

The Water Source Heat Pump Module is housed in a plastic enclosure. It
is designed to be mounted by using the 3 mounting holes in the enclosure
base. It is important to mount the module in a location that is free from
extreme high or low temperatures, moisture, dust, and dirt. Be careful
not to damage the electronic components when mounting the module.
See Figure 2 for Module dimensions (dimensions are in inches).

Figure 2: Water Source Heat Pump Module Dimensions

WATTMASTER CONTROLS

5.64

5.83

2.07

4.14

5.05

0.29

0.56

0.18 DIA. TYP. 3 PL.

Note: Height is 1.49 inches.

WattMaster Label

#LB102069-A

Rev.: 1B

E-BUS

Connector

E-BUS

Connector

+5V

PRES

GND

+24

VAC

GND

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

SUCTION
PRESSURE
TRANSDUCERS
#1 thru #4

COMP. 1 ENABLE
COMP. 2 ENABLE
COMP. 3 ENABLE

WSHP Protection Module

Orion No.: OE334-23-WPM

COMP. 4 ENABLE
HEAT ENABLE
H2O POF #1
H2O POF #2
COMMON

T 1

T 2

GND

LEAVING WATER TEMP 1

GROUND

LEAVING WATER TEMP 2

LED BLINK CODES

LED NAME

STATUS

OFF MODE

1

COOLING MODE

2

HEATING MODE

3

LED NAME

ALARM

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

WATER FLOW FAILURE

3

LOW LEAVING WATER TEMP.

4

LED NAME

PRES 1-4

SENSOR DETECTED

ON

NO SENSOR DETECTED

OFF

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

AO1

A2O

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. #2 ENABLE

COMP. #1 ENABLE

R1

R2

R3

R4

RC

RELAY COMMON

COMP. #3 ENABLE

COMP. #4 ENABLE

SYSTEM A - CNTRLR C2

SYSTEM B - CNTRLR C2

+5V

PRES

GND

NOT USED

DIGITAL COMP #1 THRU #4

NON-DIGITAL COMP #1 THRU #4

COPELAND CNTRLR P6
COPELAND CNTRLR P5

AAON No.: R90680

WattMaster Label

#LB102069-A

Rev.: 1F

E-BUS

Connector

E-BUS

Connector

+24

VAC

GND

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

COMP. A1 ENABLE
COMP. A2 ENABLE
COMP. B1 ENABLE

WSHP Module

Orion No.: OE334-23-WPM-A

AAON No.: R88350

www.aaon.com

www.orioncontrols.com

COMP. B2 ENABLE
HEAT ENABLE
WATER POF A
WATER POF B
COMMON

T 1

T 2

GND

LEAVING WATER TEMP A

GROUND

LEAVING WATER TEMP B

LED BLINK CODES

LED NAME

STATUS

OFF MODE

1

COOLING MODE

2

HEATING MODE

3

LED NAME

ALARM

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

WATER FLOW FAILURE

3

LOW LEAVING WATER TEMP.

4

LED NAME

PRES 1-4

SENSOR DETECTED

ON

NO SENSOR DETECTED

OFF

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

AO1

A2O

STAGE 1- COMP. A1/B1-

STAGE 2 - COMP. A2/B2

DIGITAL COMP. A1, A2, B1, B2

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5
RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO CNTLR C2 TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

LW: 36ºF HSP: 100 PSIG