Setpoint screen #3, Setpoint screens #4, Setpoint screens #5 – Orion System MODGAS II User Manual

Page 20: Setpoint screens #6

Advertising
background image

Section 2

MODGAS II Controller

2-4 Programming

Setpoint Screen #3

Minimum

Default Maximum

PID LOOP Period

0 sec.

15 sec.

100 sec.

Setpoint Screens #4


Minimum

Default

Maximum

Switch To HI Speed
Fan Above Sig

0%

40%

100%

Setpoint Screens #5


Minimum

Default

Maximum

Temp Above

50

°F 150°F

300

°F

Setpoint Screens #6


Minimum

Default

Maximum

Supply Sensor SAT

-100.0

° 0.0°F +100.0°F


This value represents the sampling interval of the PID loop. It
indicates the time in seconds between calculations.

This is the percentage open of the modulating gas valve where the
Hi-Speed fan is required for proper induced airflow in the heat
exchanger.

If the Supply Air Temperature ever exceeds this value, the
MODGAS II Controller will immediately be disabled. In order
for the MODGAS controller to be re-enabled (resume normal
operation), the temperature must drop 10

°F below this setpoint.

The Thermistor Type III sensor readings can be calibrated. Enter
a Positive value to increase a reading and a Negative value to
decrease a reading.

Controller Setpoints

Switch To HI Speed

Fan Above Sig: xxx%

Controller Setpoints

PID LOOP PERIOD

Seconds......: xxx s

Controller Setpoints

SUPPLY CUT-OFF

Temp. Above..: xxx°F

Controller Setpoints

Sensor Calibration

SAT: xx.x° xx.x°