Air for combustion and ventilation – Desa LCR26PT User Manual

Page 6

Advertising
background image

www.desatech.com

121255-01A

6

DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION

Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have
a confined or unconfined space.

Space: Includes the room in which you will install
heater plus any adjoining rooms with doorless pas-
sageways or ventilation grills between the rooms.
1. Determine the volume of the space (length

x width x height).

Length x Width x Height =__________cu. ft.
(volume of space)

Example: Space size 20 ft. (6.1 m) (length) x 16
ft. (4.88 m) (width) x 8 ft. (2.44 m) (ceiling height)
= 2560 cu. ft. (72.49 m

3

) (volume of space)

If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can support.

________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)

Example: 2560 cu. ft. (72.49 m

3

) (volume of

space) x 20 = 51,200 (maximum Btu/Hr the
space can support)

3. Add the Btu/Hr of all fuel burning appliances

in the space.

Vent-free heater

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________ Btu/Hr

Gas fireplace logs

__________ Btu/Hr

Other gas appliances*+ __________ Btu/Hr

Total

= _________ Btu/Hr

* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.

Example:

Gas water heater

__________ Btu/Hr

Vent-free heater

+ _________ Btu/Hr

Total

= _________ Btu/Hr

4. Compare the maximum Btu/Hr the space can

support with the actual amount of Btu/Hr used.

_______ Btu/Hr (maximum can support)

_______ Btu/Hr (actual amount used)

Example: 51,200 Btu/Hr (maximum the

space can support)

60,000 Btu/Hr (actual amount of
Btu/Hr used)

AIR FOR COMbUSTION

AND VENTILATION

Continued

The space in the above example is a confined
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can sup-
port. You must provide additional fresh air. Your
options are as follows:
A. Rework worksheet, adding the space of an

adjoining room. If the extra space provides
an unconfined space, remove door to adjoin-
ing room or add ventilation grills between
rooms. See Ventilation Air From Inside
Building.

B. Vent room directly to the outdoors. See

Ventilation Air From Outdoors, page 7.

C. Install a lower Btu/Hr heater, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconfined space. You will need no additional
fresh air ventilation.

WARNING: If the area in which

the heater may be operated is

smaller than that defined as

an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air

by one of the methods described

in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section 5.3

or applicable local codes.

vENTILATION AIR

Ventilation Air From Inside Building
This fresh air would come from an adjoin-
ing unconfined space. When ventilating to
an adjoining unconfined space, you must
provide two permanent openings: one within
12" (30.5 cm) of the ceiling and one within
12" (30.5 cm) of the floor on the wall con-
necting the two spaces (see options 1 and 2,
Figure 2, page 7). You can also remove door
into adjoining room (see option 3, Figure 2,
page 7). Follow the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation
for required size
of ventilation grills or ducts.

40,000
20,000
60,000

Advertising
This manual is related to the following products: