REMKO ASF 100 User Manual

Page 7

Advertising
background image

7

POWERFUL

This is the most powerful mode.


relative humidity 45 – 55%
- max. dehumidification capacity
- max. fan setting
relative humidity below 45%
- dehumidification off
- max. fan setting

„AUTO SWING“ button
This button is used to activate

the oscillating function of the air

directing flap.

Pressing the button again stops the

flap at the respective position. The

most favourable air flow position

can be selected in this way.

The swing function serves to

improve the air distribution within

the room.

The following information must

also be observed:

Free air flow must be ensured.

This ensures optimal unit
operation!

It must be ensured that sensi-

tive items, e.g. indoor plants
are not placed directly in the air
flow.

After 12 hours operation at
maximum power, the control
automatically selects the min.
power setting.

ATTENTION

Unit commissioning

1. Connect the units

to a properly fused
power socket.

2. Press the ON/OFF

button on the control
panel.

3. The air directing flap at the top

of the unit opens fully. The unit
is the „NORMAL“ mode and
the ioniser and timer are not
activated.

4. Select the required mode with

the „MODE“ button.

NOTE

As long as the unit is not
disconnected from the power
supply, the last selected mode
(MODE, IONIC, and AUTO
SWING) is active when the
unit is switched on.

NORMAL
This is the comfort mode.

The unit regulates according to
time (12 hours) or on reaching
the preset humidity, the dehu-
midification capacity and fan
setting.

relative humidity above 55%

- max. dehumidification

capacity

- moderate fan setting

relative humidity 45 – 55%
- min. dehumidification

capacity

- min. fan setting

relative humidity below 45%
- dehumidification off
- min. fan setting

SILENT
This is the most silent mode.

Optimal for night operation.

Relative humidity above 45%
- min. dehumidification
capacity
- min. fan setting
relative humidity below 45%
- dehumidification off
- min. fan setting

Mode

Power consumption

Fan setting

Relative humidity

NORMAL

2. Setting / 560W

medium

above 55%

1. Setting / 340W

min.

45 - 55%

min.

below 45%

SILENT

1. Setting / 340W

min.

above 45%

min.

below 45%

POWERFUL

2. Setting / 560W

max.

45 - 55%

max.

below 45%

Electronic program sequence

After 12 hours continuous operation at max. power setting, the control
automatically selects the min. power setting.
If the relative humidity subsequently falls below 45%, the dehumidifica-
tion function is switched off.
The fan continues to run at minimum speed for moisture measurement. If
the relative humidity subsequently rises above a value of 45% again, the
minimum dehumidification setting is activated. Return to the maximum
power setting can only take place via the ON/OFF button manually.

Advertising