Remko wkf duo – REMKO WKF-120-180Duo Electrical wiring User Manual

Page 14

Advertising
background image

n

If the outdoor unit is installed on a roof, it and

the supporting structure must be earthed sepa-

rately (by connecting them to a lighting con-

ductor or foundation earth electrode).

n

With the series WKF 180 Duo, make sure that

on terminals L1(R), L2(S), L3(T) and N are

connected (see Fig. 9).

1

Fig. 8: Connection terminals - Outdoor unit

WKF 120 Duo

1: Power supply 230V/1~ /50Hz

Fig. 9: Connection terminals - Outdoor unit

WKF 180 Duo

NOTICE!

Make sure to connect the outdoor unit neutral

connector properly, otherwise the varistors on

the line-filter circuit board will be destroyed.

Temperature probes

n

The number of probes required can vary with

the type of system.

n

Observe the pertinent notes for the probe posi-

tion found in the hydraulic schematic.

n

The standard model includes an external probe

(S10) and an immersion probe (intended for

use as a custom hot-water probe (S08)).

n

If a solar plant is connected, a PT-1000 probe

(S01) must be used as a collector probe and a

PT-1000 probe (S02) as a bottom storage tank

probe.

n

All probes are to be connected to the indoor

unit switching cabinet in accordance with the

connection diagram.

Contact probe

Contact probes can be mounted on the pipes, to

measure the heating-circuit temperatures, for

example.

n

The contact probe is fastened to a pipe with

the trapezoidal brackets and retaining strap

provided.

n

Clean the mounting point on the pipe. Subse-

quently a thermal compound (A) is applied and

the probe is fixed in position.

Fig. 10: Fastening the contact probe in place

If the sensor cables are too short, they can be

extended up to a maximum of 100m with wire

having a cross-section of 1.5 mm².

REMKO WKF Duo

14

Advertising