Test
Visual
Earth Continuity
Insulation
PE Conductor
Current
Touch Current
Substitute
Leakage
Wiring
RCD
Trip
Time
Name
Duration
(s)
Limit
(Ω)
Duration
(s)
Voltage
Limit
(MΩ)
Duration
(s)
Limit
(mA)
Duration
(s)
Limit
(mA)
Duration
(s)
Limit
(mA)
Limit
(ms)
Mov/Stat CLII 500V Insulation
Yes
2
500
2
Mov/Stat CLI PE Current
Yes
5
0.1
2
250
1
5
3.5
Mov/Stat CLII Touch Current
Yes
2
250
2
5
3.5
110V Handheld/Portable CLI
Yes
5
0.1
2
500
1
2
0.8
110V Handheld/Portable CLII
Yes
2
500
2
2
0.3
110V Movable/Stationary CLI
Yes
5
0.1
2
500
1
2
3.5
110V Movable/Stationary CLII
Yes
2
500
2
2
0.3
110V 25m Lead
Rpe&Insulation
Yes
5
0.5
2
500
1
Visual Only