Seaward Supernova User Manual
Page 33

How to perform Automatic Tests
23
Review Test Results
Display the results from the test in tabular form:-
APPLIANCE :
A1212654673891
SITE
USER
: KITCHEN
: BOB
TESTCODE1 :
1027353823
TESTCODE 2
: 312169743A
TEST OUTPUT
LIMIT
RESULT
STATUS
EARTH BOND
25A
0.1ohms
0.99
PASS
EARTH BOND
25A
0.1ohms
0.98
PASS
INSULATION 500V 2Mohms
20.67 PASS
SUB LEAKAGE
7.5mA
<0.25
PASS
LOAD
2.00kVa
A fast key may illuminate to ‘view comments’.
Use the Red button to return to the previous menu.
Print Pass/Fail Label
A pass or fail label can be printed using a compatible printer - see
Chapter 6. Use the Green button to start the print. The following
message will be displayed:-
PRINTING PASS/FAIL LABELS
PRESS THE RED BUTTON TO
ABORT
On completion, the Search menu is displayed.
If there are problems downloading e.g. due to interfacing problems,
then after a delay, the following error message appears:-
----------WARNING-----------
DOWNLOAD FAILED
CHECK CONNECTIONS
AND TRY AGAIN