Appendix b reference – Seaward Supernova User Manual
Page 93
Advertising

Operation Test
83
Appendix B Reference
Information Factory-set Test Sequences
Name Earth
Bond
Insulation Leakage Touch
Leakage
Flash
230V
Household 1
0.1
Ω 0.5MΩ 0.75mA
0.5
mA SKIP
230V
Household 2
SKIP 1.0M
Ω 0.25mA
SKIP SKIP
IT Equip. 1
0.1
Ω 0.5MΩ SKIP SKIP SKIP
IT Equip. 2
SKIP
1.0M
Ω SKIP SKIP SKIP
Hand-held
230V Power
Tools 1
0.1
Ω 0.5MΩ 0.75mA
0.5
mA 1.5mA
Hand-held
230V Power
Tools 2
SKIP 1.0M
Ω 0.25Ma
SKIP 1.5mA
Lead (3m)
230V
0.08
Ω 0.5MΩ SKIP SKIP SKIP
Lead (6m)
230v
0.2
Ω 0.5MΩ SKIP SKIP SKIP
Lead (12m)
230v
0.3
Ω 0.5MΩ SKIP SKIP SKIP
110V H H
Powertools 1
0.1
Ω 0.5
0.5
0.5
1.5mA
110 V H H
PowerTools
2
SKIP 1.0
0.25
SKIP 1.5mA