Installation – Desa WMN20A User Manual

Page 13

Advertising
background image

www.desatech.com

124002-01C

13

* A CSA design-certified equipment shutoff
valve with 1/8" NPT tap is an acceptable al-
ternative to test gauge connection. Purchase
the optional CSA design-certified equipment
shutoff valve from your dealer.

Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap

Test Gauge Connection*

3/8" NPT
Pipe Nipple

Heater
Cabinet

Equipment
Shutoff
Valve*

3"
Min.

Natural Gas

From Gas

Meter

(4" W.C. to

10.5" W.C. Pressure)

Propane/LP

From External Regulator

(11" W.C. to 14" W.C.

Pressure)

Ground Joint
Union

IMPORTANT: Hold the pressure regulator
with wrench when connecting it to gas pip-
ing and/or fittings. Do not over tighten pipe
connection to regulator. The regulator body
could be damaged.

Tee Joint
Pipe
Nipple
Cap

Sediment

T

rap

INsTallaTIoN

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

CAUTION: For propane/LP

gas, make sure external regula-

tor has been installed between

propane/LP supply and heater.

See guidelines under Connect-

ing to Gas Supply, page 12.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance

main gas valve (control valve) and equip-
ment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig
will damage heater regulator.

2. Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.

4. Check all joints of gas supply piping sys-

tem. Apply a noncorrosive leak detection
fluid to all joints. Bubbles forming show a
leak.

5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff

valve to gas supply. Check reconnected
fittings for leaks.

Figure 15 - Gas Connection

Pressure
Regulator

Connection Using Flexline

3/8" NPT/
1/2" Flare
90° Elbow

Flexline

See

illustration

above for

detail

Refer to connector's
instructions