Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-

ure 16).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.

3. Check all joints from gas meter for natural

gas (see Figure 17) or propane/LP supply
tank for propane/LP gas, to equipment
shutoff valve (see Figure 18). Apply a
noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak.

4. Correct all leaks at once.

PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Fig-

ure 16).

2. For natural gas open main gas valve lo-

cated on or near gas meter. For propane/
LP gas open propane/LP supply tank
valve.

3. Make sure control knob of heater is in the

OFF position.

4. Check all joints from equipment shutoff

valve to thermostat gas valve (see Figure
17 or 18). Apply a noncorrosive leak de-
tection fluid to all joints. Bubbles forming
show a leak.

5. Correct all leaks at once.
6. Light heater (see Operation, page 15).

Check all other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to

Appliance, page 16).

8. Replace front panel.

Figure 18 - Checking Gas Joints for

Propane/LP Gas (actual heater may vary

from illustration)

Equipment Shutoff Valve

Propane/LP
Supply Tank

Thermostat Gas Valve

Figure 17 - Checking Gas Joints for

Natural Gas (actual heater may vary from

illustration)

Equipment Shutoff Valve

Gas
Meter

Thermostat Gas Valve

INsTallaTIoN

Continued

Figure 16 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff Valve