5.2

Connect ONLY the TE device to the controller:

Positive TE device terminal to WP2

Negative TE device terminal to WP1

TE Technology’s standard thermoelectric cooling assemblies (TCA) have at least one fan on the heat sink.

The standard configuration has the thermoelectric modules and fan(s) wired to a terminal block with

jumpers across the terminals so that the fans and modules are connected in parallel. However, this

configuration is applicable only when applying power directly from the power supply. When using the TCA
with the temperature controller, the jumpers

MUST

be removed so that the controller is controlling

power only to the thermoelectric modules. There must be no electrical connection between the fans and

the modules; fans must be connected directly to the power supply, not to the controller. The controller

will be damaged if this is not followed. See the cooler manual for further details, but the picture below

shows the basic setup.

NOTE: Generally there is approximately a 0.5 to 1.3 V drop from the power supply to the TE device. You might

need to adjust the power supply accordingly to ensure full power is delivered to the TE device when needed.