18. LOW EXTERNAL SET RANGE

Write Command: 20

Read Command: 54

Interpret:

Value mapped to zero voltage of Input2. Only integer values are allowed.

Remember to convert to hexadecimal before sending.

19. HIGH EXTERNAL SET RANGE

Write Command: 21

Read Command: 55

Interpret:

Value mapped to 5 volt or maximum voltage of Input2. Only integer values

are allowed. Remember to convert to hexadecimal before sending.

20. ALARM DEADBAND

Write Command: 22

Read Command: 56

Interpret:

Temperature Input1 must move to toggle alarm output. When writing, first

multiply the desired deadband setting by 100

10

and convert to hexadecimal

for the “send value.” When reading, convert the “return value” to decimal

and divide by 100

10

to covert to °F/°C.

21. HIGH ALARM SETTING

Write Command: 23

Read Command: 57

Interpret:

Temperature reference to compare against Input1 for high alarm output.

When writing, first multiply the desired setting by 100

10

and convert to

hexadecimal for the “send value.” When reading, convert the “return value”

to decimal and divide by 100

10

to covert to °F/°C.

22. LOW ALARM SETTING

Write Command: 24

Read Command: 58

Interpret:

Temperature reference to compare against Input1 for low alarm output.

When writing, first multiply the desired setting by 100

10

and convert to

hexadecimal for the “send value.” When reading, convert the “return value”

to decimal and divide by 100

10

to covert to °F/°C.

23. CONTROL DEADBAND SETTING

Write Command: 25

Read Command: 59

Interpret:

Temperature or count span Input1 must move to toggle control output.

When writing, first multiply the desired setting by 100

10

and convert to

hexadecimal for the “send value.” When reading, convert the “return value”

to decimal and divide by 100

10

to covert to °F/°C.

24. INPUT1 OFFSET

Write Command: 26

Read Command: 5a

Interpret:

Value to offset Input1 by in order to calibrate external sensor if desired.

When writing, first multiply the desired setting by 100

10

and convert to

hexadecimal for the “send value.” When reading, convert the “return value”

to decimal and divide by 100

10

to covert to °F/°C.