1 INSTALLATION

1.1 Mounting

The MC-01 control instrument is housed in a DIN 96 x 96 type plastic case intended to be mounted in a

front panel of an electrical control panel via a 90 x 90 mm +0.5mm/-0mm square hole. The electrical control
panel should have a minimum depth of 190 mm behind the front panel to take the MC-01.





















IMPORTANT : In order to comply with the electrical safety requirements as per IEC 1010-1, the installation
of the equipment must take into account the following:

-

The equipment must be installed in the front panel of an electrical mounting cabinet, leaving
only the front of the equipment accessible to the operator.

-

A mains switch must be provided to disconnect the equipment. This switch must be marked
as the disconnecting device for the equipment and be within easy reach of the operator.

-

The mains supply must have an earth line.

1.2

Mains Connection

The connection of the equipment is via plug-in connectors, polarized to avoid mistakes when plugged

in. The connectors have screw terminals, as per VDE norms, to accept 1,5 mm

2

cable.

When we refer to the positions of the connectors, it is looking at the back of the MC-01.

The connector for the mains power supply is situated on the bottom right-hand side, in which the

power supply (voltage indicated below the connector) must be connected to terminals Nº1 and Nº2.
Terminal Nº3 should be connected to a good earth. The MC-01 has a Φ 5 x 20 mm mains fuse inside. The
nominal rating of this fuse depends on the mains voltage.