Location of termination cap – Desa (V)T32EN User Manual

Page 6

Advertising
background image

www.desatech.com

108860-01D

6

Fixed

Closed

Openable Fixed

Closed

Openable

V

V

V

V

V

V

V

V

X

X

V

X

G

G

J

F

B

B

K

N

H

I

A

N

E

L

D

B

M

A

C

B

V

V

A

G

G

B

TERMINATION CAP

AIR SUPPLY INLET

GAS METER

RESTRICTED AREA
(TERMINATION PROHIBITED)

A = clearance above grade, veranda, porch, deck, or balcony
[*12" (30.5 cm) minimum]
B = clearance to window or door that may be opened
[12" (30.5 cm) minimum]
C = clearance to permanently closed window [minimum 12" (30.5 cm)
recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24" (61cm) from the
center-line of the terminal [18" (45.7 cm) minimum]
E = clearance to unventilated soffit [12" (30.5 cm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly within
36" (91.4 cm) horizontally from the center-line of the regulator

I = clearance to service regulator vent outlet [*72" (182.9 cm)
minimum]
J = clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other fireplace [*12" (30.5 cm)
minimum]
K = clearance to a mechanical air supply inlet [*72" (182.9 cm)
minimum]
L = † clearance above paved side-walk or a paved driveway located on
public property [*84" (213.3 cm) minimum]
M = clearance under veranda, porch, deck [*12" (30.5 cm) minimum ‡]
N = clearance above a roof shall extend a minimum of 24" (61 cm)
above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18" (45.7 cm)

† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
*

as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.

Note: Local codes or regulations may require different clearances

A = 6" (15.2 cm)

Inside Corner

V

B

E

V

B = 6" (15.2 cm)

C = Maximum depth of 48" (121.9 cm) for

recessed location

D = Minimum width for back wall of

recessed location -

Combustible - 38" (96.5 cm)

Noncombustible - 24" (61cm)

E = Clearance from corner in

recessed location-

Combustible - 6" (15.2 cm)

Noncombustible - 2" (5.1 cm)

Outside Corner

Recessed Location

G

H

G = 12" (30.5 cm) minimum clearance

Balcony with No Side Wall

V

J

Combustible &
Noncombustible
H = 24" (61 cm)
J = 20" (50.8 cm)

Balcony with Perpendicular Side Wall

C

D

C

Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

Figure 7 - Minimum Clearances for Termination Cap